Fujitsu BACnet UTY-VBGX Instruction Manual page 77

Gateway for vrf system
Table of Contents

Advertisement

BACnet
®
Gateway for VRF System
5.3.54 OU_rr_uu_LowNoiseOp_Status (Multistate Input Object Type)
Low noise operation status for an outdoor unit can be monitored.
Property Identifier
Object_Identifier
Object_Name
Object_Type
Present_Value
Description
Device_Type
Status_Flags
Event_State
Reliability
Out_Of_Service
Number_Of_States
State_Text
Time_Delay
Notification_Class
Alarm_Values
Fault_Values
Event_Enable
Acked_Transitions
Notify_Type
Event_Time_Stamps
Profile_Name
* Only available when specific object has a Notification Class configured
Low Noise Operating status table
Low Noise Operation Status can be checked using the values in the following correspondence table.
Pesent_Value Contents displayed in State_Text
1
Not Set
2
-/-/E
3
-/A/-
4
-/A/E
5
1/-/-
6
1/-/E
7
1/A/-
8
1/A/E
Property Datatype
BACnetObjectIdentifier
CharacterString
BACnetObjectType
Unsigned
CharacterString
CharacterString
BACnetStatusFlags
BACnetEventState
BACnetReliability
BOOLEAN
Unsigned
BACnetArray[N] of
CharacterString
Unsigned
Unsigned
List of Unsigned
List of Unsigned
BACnetEventTransitionBits
BACnetEventTransitionBits
BACnetNotifyType
BACnetArray[N] of
BACnetTimeStamp
CharacterString
Copyright© 2010-2017 Fujitsu General Limited - All rights reserved
INSTRUCTION MANUAL r1.3.2 eng
Value
(Multistate Input, 32rruu)
"OU_rr_uu_LowNoiseOp_Status"
MULTISTATE_INPUT (13)
1 ~ 16
-
-
{FALSE, FALSE/TRUE, FALSE, FALSE}
STATE_NORMAL (0)
NO_FAULT_DETECTED (0),
UNRELIABLE_OTHER (7)
FALSE
16
Check Low Noise Opeation status below
-
-
-
-
-
-
-
-
-
Pesent_Value
Contents displayed in State_Text
9
2/-/-
10
2/-/E
11
2/A/-
12
2/A/E
13
3/-/-
14
3/-/E
15
3/A/-
16
3/A/E
UTY-
ASHRAE
VBGX
R
R
R
R
R
R
R
R
O
-
O
-
R
R
R
R
O
R
R
R
R
R
O
R
O
R*
O
R*
O
R*
O
R*
O
R*
O
R*
O
R*
O
R*
O
-
77/103

Advertisement

Table of Contents
loading

Table of Contents