PPO TYPE NON-SUPPORT SPECIFICATION
8.7

PROFIBUS PNU (Module type E5NP)

8.7.1

Real-time monitor area (IND=0000H (IND=00H, PP=00H))

The following items can be monitored from the master.
IND
PNU
0000H 0H Output frequency
0000H 1H Output current
0000H 2H Output voltage
0000H 4H Frequency setting
0000H 6H Motor torque
0000H 7H Converter output voltage
0000H 8H Regenerative brake duty
Electronic thermal relay
0000H 9H
function load factor
0000H AH Output current peak value
Converter output voltage
0000H BH
peak value
0000H DH Output power
*1
Input terminal monitor details (when the terminal is ON: 1, when the terminal is OFF: 0,
b15
Functions of each terminal are assigned using Pr.178 to Pr.184. (Refer to the inverter manual for details)
*2
Output terminal monitor details (when the terminal is ON: 1, when the terminal is OFF: 0,
b15
Functions of each terminal are assigned using Pr.190 to Pr.192. (Refer to the inverter manual for details)
72
Item
Increments
0.01Hz
0.01A
0.1V
0.01Hz
0.1%
0.1V
0.1%
0.1%
0.01A
0.1V
0.01kW
RES
IND
PNU
0000H EH Input terminal status
0000H FH Output terminal status
0000H 13H Cumulative energization time
0000H 16H Actual operation time
0000H 17H Motor load factor
0000H 18H Cumulative power
0000H 33H PID set point
0000H 34H PID measured value
0000H 35H PID deviation
0000H 3CH Motor thermal load factor
0000H 3DH Inverter thermal load factor
0000H 3EH Cumulative power 2
RH
RM
ABC
Item
Increments
*1
*2
1h
1h
0.1%
1kWh
0.1%
0.1%
0.1%
0.1%
0.1%
0.01kWh
: unfixed value)
RL
STR
: unfixed value)
FU
b0
STF
b0
RUN