Mitsubishi Electric AJ65VBTCU-68DAVN User Manual page 96

Programmable controller digital-analog converter module
Hide thumbs Also See for AJ65VBTCU-68DAVN:
Table of Contents

Advertisement

5 PROGRAMMING
Procedure Execution Condition in AJ65VBTCU-68DAVN
Initial data processing request flag (RX18) turns ON
Initial data processing request flag (RX18) turns OFF
Initial data setting completion flag (RX19) turns ON
5 - 30
(e) Selection of procedure registration (part 2)
Make setting for the AJ65VBTCU-68DAVN.
Click Procedure registration of target station number "4".
(f)
Setting of procedure registration (part 2)
Set the conditions and execution for the AJ65VBTCU-68DAVN.
When the initial data processing request flag (RX18) turns ON and Remote
device station initialization procedure registration (SB0D) is set, the
following data are registered to the AJ65VBTCU-68DAVN.
Analog output enable/prohibit setting: Channel 1, 2: Enable (RWw8: 00FC
CH. 1 to CH. 4 input range setting : Channel 1: 0 to 5V
(RWw9: 0031
HOLD/CLEAR setting: Channel 1, 2: CLEAR (RWwB: 0
Initial data processing completion flag (RY18) is turned ON.
Initial data setting request flag (RY19) is turned ON.
Initial data processing completion flag (RY18) is turned OFF.
Initial data setting request flag (RY19) is turned OFF.
(g) Setting result (part 2)
The following indicates the setting result of the AJ65VBTCU-68DAVN.
POINT
(1) If the remote device station initialization procedure registration command
(SB000D) is turned OFF after initial processing, all RY signals that turned ON
in the initial procedure registration turn OFF. Hence, turn ON "CH.
output enable/prohibit flag (RYn0 to RYn7)" in the sequence program.
(2) When the initial setting (analog output enable/prohibit setting (RWwn+8), CH.
output range setting (RWwn+9, RWwn+A), HOLD/CLEAR setting (RWw+B)),
the remote device station initialization procedure registration function cannot be
used.
Change the initial setting in the sequence program.
(3) When the remote device station initialization procedure registration function is
not used but a sequence program is used to make setting, refer to the user's
manual of the used master module.
Execution Data
: Channel 2: User range setting 1
)
H
MELSEC-A
)
H
)
H
analog
5 - 30