5 PROGRAMMING
5 - 27
(3) Initial settings
Remote Device Station
AJ65VBTCU-68ADV
AJ65VBTCU-68DAVN
(4) Other settings
Remote Device Station
AJ65VBTCU-68DAVN
POINT
When using the AJ65VBTCU-68DAVN as the ver. 2 remote device station in the
normal mode, set the mode select switch to "3".
Setting Item
A/D conversion enable/prohibit
specification (RWw0)
CH. 1 to CH. 4 input range
setting (RWw1)
Average processing specification
(RWw3)
CH. 2 average time, number of
times setting (RWw5)
Analog output enable/prohibit
setting (RWw8)
CH. 1 to CH. 4 output range
setting (RWw9)
HOLD/CLEAR setting (RWwB)
Setting Item
CH. 1 digital value (RWw0)
CH. 2 digital value (RWw1)
CH. 1 analog output
enable/prohibit flag (RY00)
CH. 2 analog output
enable/prohibit flag (RY01)
MELSEC-A
Settings
A/D conversion enable channel:
Channel 1, 2
Channel 1: 0 to 5V
Channel 2: User range setting 1
Channel 1: Sampling
processing
Channel 2: Average processing,
number of times averaging
Number of average processing
times of channel 2: 16 times
Channel 1, 2: Enable
Channel 1: 0 to 5V
Channel 2: User range setting 1
Channel 1, 2: CLEAR
Settings
500
1000
Enable
Enable
5 - 27