Advertisement

5 PROGRAMMING
Procedure Execution Condition in AJ65VBTCU-68ADV
Initial data processing request flag (RX18) turns ON
Initial data processing request flag (RX18) turns OFF
Initial data setting completion flag (RX19) turns ON
5 - 21
(2) Initial setting by remote device station initialization procedure
registration function
(a) Setting of target station numbers
Set the station numbers to which initial setting will be made.
Set the target station numbers to "1" and "4".
(b) Selection of procedure registration (part 1)
Make setting for the AJ65VBTCU-68ADV.
Click Procedure registration of target station number "1".
(c) Setting of procedure registration (part 1)
Set the conditions and execution for the AJ65VBTCU-68ADV.
When the initial data processing request flag (RX18) turns ON and Remote
device station initialization procedure registration (SB0D) is set, the
following data are registered to the AJ65VBTCU-68ADV.
A/D conversion enable/prohibit specification: Channel 1, 2: Enable (RWw0: 0003
CH. 1 to CH. 4 input range setting : Channel 1: 0 to 5V
(RWw1: 31
Average processing specification : Channel 1: Sampling processing
(RWw3: 200
CH. 2 average time, number of times setting: Channel 2: 16 times (RWw5: 10
Initial data processing completion flag (RY18) is turned ON.
Initial data setting request flag (RY19) is turned ON.
Initial data processing completion flag (RY18) is turned OFF.
Initial data setting request flag (RY19) is turned OFF.
(d) Setting result (part 1)
The following indicates the setting result of the AJ65VBTCU-68ADV.
Execution Data
: Channel 2: User range setting 1
)
H
: Channel 2: Average processing, number of times averaging
)
H
MELSEC-A
)
H
)
H
5 - 21