Input / Output Testing Functions - Fujitsu Waterstage Comfort Series Maintenance Document

Air to water heat pump, refrigerant r410a inverter, outdoor/hydraulic unit
Table of Contents

Advertisement

Split system single phase type

4 5 8 Input / Output Testing Functions

Input/output testing is used to ensure that the connected
components are in working order
Relay Output Testing
Selection of a setting from relay testing closes the
corresponding relay and therefore switches on the
connected component This makes it possible to check
that the relays are in working order and that the wiring
has been performed correctly
Line N°
Programming line
7700
Relay test
This consists of instructing the regulator's relays one by one and checking their outputs. This enables you to check that
the relays are working and that the cabling is correct. Check that each appliance in the installation is operating correctly.
(0) No test, (1) Everything is on STOP, (2) Relay output QX1 : heat pump CC1 (Main regulation board), (3) Relay output
QX2 : Electrical back-up (1st stage) or Boiler connection distribution valve, (4) Relay output QX3 : Electrical back-up
(2nd stage) or Boiler connection contact, (5) Relay output QX4 : DHW distribution valve, (6) Relay output QX5 : DHW
Electrical back-up, (7) Relay output QX6 , (8) Relay output QX31 : Heat circ mix valve open Y1, (9) Relay output QX32 :
Heat circ mix valve close Y2, (10) Relay output QX33 : heat pump CC2, (11) Relay output QX34, (12) Relay output QX35 :
Swimming pool distribution valve, (13) Relay output QX21 module 1, (14) Relay output QX22 module 1, (15) Relay output
QX23 module 1, (16) Relay output QX21 module 2, (17) Relay output QX22 module 2, (18) Relay output QX23 module
2, (19) Not used, (20) Not used, (21) Not used.
The display shows the "Key" symbol. Pressing the Info button displays "Error 368".
Warning: The component being tested is receiving electrical power throughout the test.
Analog Input/Output Testing
Line N°
7710
7712
7722
7723
7724
7725
Output test UXx :
Enables testing the outdoor unit control
Cooling mode DOx :
Shows the output status
Sensor Input Testing
Line N°
Programming line
7820
Sensor temp BX1
7821
Sensor temp BX2
7822
Sensor temp BX3
7823
Sensor temp BX4
Displays the temperature of each sensor
Maintenance document "1792 - EN"
Programming line
Output test UX1
PWM signal UX1
Cooling mode DO2
Heat pump D3
Output test UX3
Voltage value UX3
Warning:
During testing of an output, the heat pump is stopped,
all outputs are "off" and only the controlled output is on
Input test EX1-3
Line N°
Programming line
7911
Input EX1
7912
Input EX2
7913
Input EX3
By selecting a setting from input test EX1-3, the relevant
input will be displayed, enabling it to be checked
Display of 0 V means that there is no voltage and the
respective input is currently inactive Display of 230 V
means that voltage is present at the respective input so
that it is activated
Input / output test I/O module
Line N°
Programming line
7973
Sensor temp BX31
7976
Sensor temp BX34
7996
Contact state H33
The sensor test operate the same as for BX1-4 on the
basic unit
- 85 -