Electrical System - Fujitsu Waterstage Comfort Series Maintenance Document

Air to water heat pump, refrigerant r410a inverter, outdoor/hydraulic unit
Table of Contents

Advertisement

Split system single phase type

3 1 2 Electrical System

Outdoor Unit Overvoltage
Check for possible causes in the list below (this list is
not exhaustive):
Problem with the compressor
Main board
Faulty power relaySteps to be followed before
performing any work on the Inverter module:
Inspection of the IPM (mounted on transistor PCB) (Only for WOYA080LFCA and
Inspection of the IPM (mounted on transistor PCB) (Only for WO*A080LFCA and
WOYA100LFTA models)
WO*A100LFTA models)
transistor PCB-Capacitor PCB and Transistor PCB-
Inverter compressor
Set the tester to resistance mode, and measure the
resistance between the following terminals :
TM301 (P) – TM305 (U) / TM304 (V) / TM303 (W)
TM302 (N) – TM305(U) / TM304 (V) / TM303 (W)
Judge the results as follows :
Terminal
Tester (+)
Tester (-)
P
U
P
V
P
W
U
P
V
P
W
P
N
U
N
V
N
W
U
N
V
N
W
N
- 40 -
Resistance value
Over 2kΩ
(Including ∞)
Over 20kΩ
(Including ∞)
Over 2kΩ
(Including ∞)
First switch off the system using the circuit
breaker at the head of the line
Remove the unit cover and then remove the
Inverter module cover
Measure the voltage at the condenser terminals
You should find a value of 5 Vdc or less
WOYA080LFCA
WO*A080LFCA
WOYA100LFTA
WO*A100LFTA
Maintenance document "1792 - EN"