Input / Output Testing Functions - Fujitsu Waterstage WS G140DC6 Series Maintenance Document

Air to water heat pump. split system (single phase type). split system (3-phase type).
Table of Contents

Advertisement

Split system (Single phase and 3-phase type)
4.3.14
Input/output testing is used to ensure that the
connected components are in working order.
Relay Output Testing
Selection of a setting from relay testing closes the
corresponding relay and therefore switches on the
connected component. This makes it possible to
Line no.
Programming line
7700
Relay test
This consists of instructing the regulator's relays one by one and checking their outputs. This enables you
to check that the relays are working and that the cabling is correct. Check that each appliance in the
installation is operating correctly.
(0) No test, (1) Everything is on STOP, (2) Relay output QX1 : heat pump CC1 (Main regulation board), (3)
Relay output QX2 : Electrical back-up (1st stage) or Boiler connection distribution valve, (4) Relay output
QX3 : Electrical back-up (2nd stage) or Boiler connection contact, (5) Relay output QX4 : DHW distribution
valve, (6) Relay output QX5 : DHW Electrical back-up, (7) Relay output QX6 , (8) Relay output QX31 :
Heat circ mix valve open Y1, (9) Relay output QX32 : Heat circ mix valve close Y2, (10) Relay output
QX33 : heat pump CC2, (11) Relay output QX34, (12) Relay output QX35 : Swimming pool distribution
valve, (13) Relay output QX21 module 1, (14) Relay output QX22 module 1, (15) Relay output QX23
module 1, (16) Relay output QX21 module 2, (17) Relay output QX22 module 2, (18) Relay output QX23
module 2, (19) Not used, (20) Not used, (21) Not used.
The display shows the "Key" symbol. Pressing the Info button displays "Error 368".
Warning: The component being tested is receiving electrical power throughout the test.
Warning:
During testing of an output, the heat pump is stopped,
all outputs are "off" and only the controlled output is
on.
Analog Input/Output Testing
Line no.
Programming line
7710
Output test UX1
7712
PWM signal UX1
7722
Cooling mode DO2
7723
Heat pump D3
7724
Output test UX3
7725
Voltage value UX3
Output test UXx
Enables testing the outdoor unit control.
Sensor Input Testing
Line no.
Programming line
7820
Sensor temp BX1
7821
Sensor temp BX2
7822
Sensor temp BX3
7823
Sensor temp BX4
Displays the temperature of each sensor.
82

Input / Output Testing Functions

check that the relays are in working order and that
the wiring has been performed correctly.
Cooling mode DOx
Shows the output status.
Maintenance Document 1544-1

Hide quick links:

Advertisement