Fujitsu Waterstage Comfort Series Maintenance Document page 55

Air to water heat pump, refrigerant r410a inverter, outdoor/hydraulic unit
Table of Contents

Advertisement

Split system single phase type
Function
Line
5963
S
Input value 1 H3
5964
S
Function value 1 H3
5965
S
Input value 2 H3
5966
S
Function value 2 H3
5980
S
Function input EX1
0: None, 1: Electrical utility lock E6, 2: Low-tariff E5, 4: Overload source E14, 5: Pressure switch source E26,
6: Flow switch source E15, 7: Flow switch consumers E24, 8: Manual defrost E17, 9: Common fault HP E20,
10: Fault soft starter E25, 12: Low-pressure switch E9, 13: High-pressure switch E10, 14: Overload compressor 1 E11,
15: Error/alarm message, 16: Mains supervision E21, 18: Pressure diff defrost E28, 19: Pres sw source int circ E29,
20: Flow sw source int circ E30, 21: Smart grid E61, 22: Smart grid E62, 25: Optg mode change HCs, 26: DHW push
5981
S
Contact type input EX1
5982
S
Function input EX2
0: None, 1: Electrical utility lock E6, 2: Low-tariff E5, 4: Overload source E14, 5: Pressure switch source E26,
6: Flow switch source E15, 7: Flow switch consumers E24, 8: Manual defrost E17, 9: Common fault HP E20,
10: Fault soft starter E25, 12: Low-pressure switch E9, 13: High-pressure switch E10, 14: Overload compressor 1 E11,
15: Error/alarm message, 16: Mains supervision E21, 18: Pressure diff defrost E28, 19: Pres sw source int circ E29,
20: Flow sw source int circ E30, 21: Smart grid E61, 22: Smart grid E62, 25: Optg mode change HCs, 26: DHW push
5983
S
Contact type input EX2
5985
S
Contact type input EX3
6098
S
Readjustm collector sensor
S
6100
Readjustm outdoor sensor
6117
S
Central setp compensation
6120
S
Frost protection plant
6201
S
Reset sensors
6205
S
Reset to default parameters
6220
S
Software version (RVS)
6300
S
Info 1 OEM
6301
S
Info 2 OEM
LPB system
6600
S
Device address
Maintenance document "1792 - EN"
Setting range
or display
Normally-closed contact (NC)
Normally-opened contact (NO)
Normally-closed contact (NC)
Normally-opened contact (NO)
Normally-closed contact (NC)
Normally-opened contact (NO)
-20
20
-3
3 °C
1
100°C
On, Off
No, Yes
No, Yes
0
99
0
65535
0
65535
0
16
Setting
Basic
increment
setting
0
0
10
100
Electrical
utility lock E6
NO
Low-tariff E5
NC
NO
0
0 °C
0,1 °C
5 °C
On
No
No
--
--
--
1