Split system single phase type
Clear 14: Expansion valve thermistor error
Hydraulic Unit LED: Green 7 flashes / Red 8 flashes
Outdoor Unit LED: flash
Probable causes:
Misconnection
Sensor failure
Main PCB failure
Check:
Clear 14:
1 Check the sensor connection:
-
See if the connector has been removed
See if the connection is correct
-
Check for any damage on the sensor cable
-
After solving the misconnection problem, switch the heat pump back on
2 Remove the sensor and check its resistance value :
- Check the resistance value
Temperature (°C)
Resistance (kΩ)
168 130 101
Temperature (°C)
Resistance (kΩ)
12,3 8,7
- If the thermistor is faulty, replace it
3 Check the electronic board voltage:
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5 0V)
WOYA060LFCA
WO*A060LFCA
EXP VALVE
PIPE
DISCHARGE PIPE
OUTDOOR TEMP
- If there is no voltage, replace Main PCB
Maintenance document "1792 - EN"
OK
0
5
10
15
20
79
63
60
70
80
90
100 120
6,3
4,6
3,4
OK
WOYA080LFCA
WO*A080LFCA
COMPRESSOR
TEMP
30
40
50
40
26,3 17,8
2
COMPRESSOR
TEMP
EXP VALVE
OUTDOOR
TEMP
DISCHARGE
PIPE
PIPE
WOYA100LFTA
WO*A100LFTA
EXP VALVE
COMPRESSOR
TEMP
OUTDOOR
TEMP
PIPE
DISCHARGE
PIPE
- 17 -