Chapter 13: Replace The System Board; Verify The Status Of The System Board - Dell PowerProtect DD6900 Manual

Table of Contents

Advertisement

Complete the following procedure to replace the system board.
This FRU is not hot-swappable, and requires a system shutdown to replace.
After a system board replacement, user-configured iDRAC settings and users are reset. Those settings must be reconfigured
manually.
CAUTION:
Do not move the TPM from the old system board to the new system board. A new TPM is included
with the replacement system board.
Topics:

Verify the status of the system board

Shut down and disconnect the system
Remove a power supply
Extend the system from the cabinet
Remove the system cover
Removing the air shroud
Remove the cooling fan assembly
Remove expansion card risers
Remove the integrated storage controller card
Remove the memory module
Remove processor and heat sink module
Remove the system board
Install the system board
Install a processor and heat sink module
Install the memory module
Install the integrated storage controller card
Install expansion card riser 1
Install expansion card riser 2
Install expansion card riser 3
Install the cooling fan assembly
Installing the air shroud
Install the system cover
Install the power supply unit
Slide the system into the cabinet
Reconnect and power on the system
Restoring the Service Tag by using the Easy Restore feature
Enter the system Service Tag by using System Setup
Import server profile
Upgrade the identity module firmware
Bring up the existing file system
Restore the HA configuration
Verify the status of the system board
Prerequisites
Establish a connection to the system as described in
page 14.
Replace the system board
Establish a serial management connection to the PowerProtect system
Replace the system board
13