GFK-2738AB
Specifications
PROFINET Support
PAC Machine Edition Version
Required
Power Requirements
Operating Temperature
Range
Number of Port Connectors
FW Upgrade Connector
SD Card
PNS001 Status and Control
Bits
PROFINET I/O production rate
(I/O Update Rate)
Number of IP addresses
Number of MAC Addresses
I/O Station Maximum Limits
Configuration
For installation and maintenance requirements, refer to PACSystems RX3i Installation and Maintenance
Requirements, GFK-2975.
Descriptions
PROFINET Version 2.3 Class A I/O Device
Redundantly controlled operation implements PROFINET V2.3 Type S-2 System Redundancy
PNS001 & PNS101: Version 8.50 SIM 2 or later
PNS001-Bxxx or later:
PNS101-Axxx or later:
3.3 Vdc
0.6 A with no SFP devices installed
1.3 A maximum (two SFP devices installed,
0.35A per SFP)
PNS001-Bxxx or later:
PNS101-Axxx or later:
5Vdc: 0.7 A maximum
PNS001-Bxxx or later:
PNS101-Axxx or later:
-25°C to 60°C
Derated to 57°C:
• If 100MB Fiber SFPs installed, or
• If Copper SFPs operating at 1GB
Two RJ-45 and Two SFP Cages
PNS001-Bxxx & PNS101-Axxx:
One RJ-45 Ethernet connector on front panel
Supports SD and SDHC cards.
32 input status bits and 32 output control bits
Configurable selections: 1ms, 2ms, 4ms, 8ms, 16ms, 32ms, 64ms, 128ms, 256ms or 512ms
PNS001-Bxxx & PNS101-Axxx: Two
One for PROFINET ports.
One for front panel port. Supports Classless
Inter-Domain Routing (CIDR)
PNS001-Bxxx & PNS101-Axxx: Six
One front panel port, one for each of the four
external ports, and one internal port.
Number of I/O Modules per station
I/O data per station
V2.3 GSDML file is available for download and to import into PAC Machine Edition. Please see
the support link at the end of this document. The GSDML supporting a firmware release is part
of the firmware upgrade kit available on the Support website.
PNS001-Axxx:
3.3 Vdc
1.2 A with no SFP devices installed
1.9 A maximum (two SFP devices installed,
0.35A per SFP)
PNS001-Axxx:
1.1
5Vdc:
PNS001-Axxx:
0°C to 60°C
Derated to 57°C:
• If 100MB Fiber SFPs installed, or
• If Copper SFPs operating at 1GB
(SFP devices not included, available separately)
PNS001-Axxx:
One USB connector on front panel
PNS001-Axxx: One
One for PROFINET ports.
PNS001-Axxx: Five
One for each of the four external ports, and
one internal port.
Number of backplane slots minus one for the
PNS and at least one for a power supply
2880 bytes total
1440 bytes of input data
1440 bytes of output data
Jul 2022
A maximum
3
Need help?
Do you have a question about the PACSystems RX3i PROFINET Scanner and is the answer not in the manual?
Questions and answers