1A. Main winding
1B. Start winding
1D. Winding protector
If resistance measuring shows that there is a
12 - ACB Pressostat setting (mini HP/LP)
Application
Refrigerant
LBP
MBP
LBP
R404A
MBP
R134a
13 - Dual Pressure Switch Setting
Refrigerants
R404A/R507/R452A
R134a/R513A
4 | AN23088644237302-000301 - 118A2994A
connection through the motor windings from
points K and S of the current lead-in, but a
broken circuit between points K and F or
between S and F, this indicates that the winding
High Pressure Setting (bar)
ON
R290
16
R290
10
20
13
High pressure settings (bar (g))
ON
23
13
protector has cut out. Therefore, wait for the
protector to reset.
OFF
20
25
25
18
Low pressure settings (bar (g))
OFF
ON
27
2
17
2
Low pressure Setting (bar)
ON
OFF
0.3
-0.4
1.7
0.7
-
-
1.5
0.1
OFF
1
1
© Danfoss | Climate Solutions | 2022.05