Endress+Hauser Soliswitch FTE20 Operating Instructions Manual page 25

Point level switch
Hide thumbs Also See for Soliswitch FTE20:
Table of Contents

Advertisement

Soliswitch FTE20
9.5
Installation
9.5.1
Mounting location
Orientation(® å 2, ä 10)
Permitted
Vertical from the top
Angled from the top
From the side
From below
9.5.2
Special mounting instructions
Side load on the shaft
max.60 N
Load on the rope
max.1 500 N
Operating pressure (abs.)
0.5 to 1.8 bar (7.25 to 26.1 psi)
360 °Housing can be rotated
To adjust to the direction of the cable entries (pointing downwards)
9.6
Environment
9.6.1
Ambient temperature range
–20 to 60 °C (–4 to 140 °F)
9.6.2
Storage temperature
–20 to 60 °C (–4 to 140 °F)
9.6.3
Degree of protection
IP66
Endress+Hauser
Not permitted
In direction of solids flow
Installation socket too long
Horizontal with shaft length
>300 mm (11.8 in)
Technical data
Remarks
Cable entry must point
downwards
Cable entry must point
downwards; with protective cover
against falling solids depending on
the installation position
Cable entry must point
downwards
25