Final System Setup
After completing all of the steps previously outlined,
perform these final checks before leaving the unit:
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors
before servicing could result in death or serious
injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. Verify with a CAT III or IV
voltmeter rated per NFPA 70E that all capacitors have
discharged.
RTAC-SVX005A-EN
•
Turn the solution pump control circuit breaker handle to
the "Off" position. Inspect the unit for misplaced tools,
hardware, and debris.
•
Close the disconnect switch or circuit protector switch
that provides the supply power to the unit's circuit
breaker.
•
Turn the solution pump control circuit disconnect switch
to the "Hand or Auto" position.
•
Press the "AUTO" key at the Human Interface Module
to begin system operation.
•
The system will start automatically once a request for
solution cooling has been initiated.
•
Verify that all exterior panels including the control panel
doors and condenser grilles are secured in place.
Start-Up
39