Table 6.
Evaporator flow and pump performance
Unit Size and
Pump
Sequence
Motor Size
(Tons)
(HP)
155F0
25
155F2-F3
25
170F0
25
170F2
25
200F0
25
200F2-F3
25
250F0
40
250F2-F3
30
300F0
50
300F2-F3
50
400F0
50
400F2-F3
50
500F0
50
500F2-F4
50
Note: Table values are recommended maximum and minimum evaporator flow rates or maximum and minimum performance limits of the pump. Always keep the
flow rates within the maximum and minimum flow rates of the above table.

Pre-start Checkout

Unit Location and Mounting

1. Inspect the location for installation and verify service
access clearances.
2.
Provide adequate blocking to level trailer.

Inspection

WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could
result in death or serious injury.
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Verify that no power is
present with a voltmeter.
1. Inspect all wiring connections. Connections should be
clean and tight.
2. Energize crank case and oil separator heaters 24 hours
prior to start up.
Note: Connecting shore power to the unit without main
power energizes the crankcase and oil separator
heaters. DynaView is powered at the same time.
3. Confirm all service and isolation valves are open.
RTAC-SVX005A-EN
Evaporator
Minimum
Nominal
Flow (GPM)
Flow (GPM)
193
372
193
372
202
408
202
408
217
480
217
480
217
600
217
600
309
720
309
720
381
960
381
960
461
1200
422
1200
Maximum
Minimum
Flow (GPM)
Flow (ft)
709
129.7
709
143.2
741
129.7
741
143.2
796
129.7
796
143.2
796
117.0
796
123.1
1134
161.0
1134
142.2
1396
161.0
1396
141.9
1548
143.4
1548
145.9

Electric Wiring

Hazardous Voltage!
Failure to disconnect power before servicing could
result in death or serious injury.
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Verify that no power is
present with a voltmeter.
Check for tight connections for the unit power supply
wiring with the circuit breaker to the terminal block.
Check interlock wiring, chilled water pump control,
chilled water flow interlock and external auto stop
(required). For further details refer to RTAC-SVX01*EN
or unit wiring schematics.
If remote alarm contacts, limit warning contact,
emergency stop, external chilled water setpoint or
external current limit setpoint are used, refer to RTAC-
SVX01*EN and the unit wiring for further details.
Installation - Electrical
Pump Pressure
Nominal
Maximum Flow (ft)
Flow (ft)
104.1 @ 709 GPM
126.7
98.9 @ 606 GPM
129.4
100.5 @ 741 GPM
125.5
98.9 @ 606 GPM
125.8
93.6 @ 796 GPM
122.2
98.9 @ 606 GPM
117.0
108.8 @ 796 GPM
114.2
93.7 @ 796 GPM
111.5
123.8 @ 1134 GPM
153.8
119 @ 1134 GPM
137.3
117 @ 1168 GPM
139.3
95.2 @ 1396 GPM
128.8
93 @ 1543 GPM
117.2
86.8 @ 1522 GPM
119.2
WARNING
35