ProScan
®
Programming
This setting defines the minimum distance that the sensor will detect valid echo returns.
Note : If the Dead Band* setting is placed below the "Max Full Setting" setting, then the sensor will not measure above the Dead Band.
Extended Fitting
Dead Band
Max Full
Setting
Dead Band Area
Above Max Full
Setting
1. From the Main Screen
2.
to advance into the Programming Menu.
OK
3.
5X until menu shows Dead Band*
4.
to edit Dead Band value | Highlighted Segment
OK
5.
to move one segment to the right.
6.
to increase the value of the number highlighted
7. When the value is correct
8. When done
to return to the Main Menu
BK
Quick-Start
Dead Band
Dead Band
Max Full
Max Full
Setting
Dead Band Area
Equals Max Full
Setting
to advance into the Main Menu.
OK
to save the setting
OK
Press
Max Full
Setting
Setting
Dead Band
Dead Band Area
Below Max Fill
Setting
*Dead Band = Near Blanking
scroll to right, then back to the first digit
scroll from 0 to 9 and back again
a second time to return to the Main Screen
BK
Measurement
Location
Dead Band
Dead Band Area
Equals Max Fill
Setting
28.00
Levelpro
Basic Setting
Display
Diagnostics
Service
Info
Min Adjustment
Dist
Dead Band
Dead Band
Dead Band
ft
0.00%
32' 09" 1 ft (d)
07 05"m (d)
1.8
0.50 ft (d)
1.8
05.0 ft (d)
10