Wiring Diagrams - Trane A801X026AM2SC Installation, Operation And Maintenance Manual

Upflow/downflow/horizontal left/right gas-fired, single stage induced draft furnaces with high efficiency motor
Table of Contents

Advertisement

Wiring Diagrams

NOTES:
1. IF ANY OF THE ORIGINAL WIRING SUPPLIED WITH THIS FURNACE MUST BE REPLACED, IT MUST BE WITH WIRE
HAVING A TEMPERATURE RATING OF AT LEAST 105°C. WIRES 12, 18, 20, 48, 49, 50, 51, 92 & 93 MUST BE RATED TO 250°C.
2. FOR PROPER AIRFLOW IN COOLING/HEAT PUMP MODE, "Y1" ON THE THERMOSTAT MUST BE CONNECTED TO "Y1"
OF THE IFC. SEE INSTALLER'S GUIDE FOR FIELD WIRING.
3. THE INDOOR BLOWER MOTOR AIRFLOW TABLES ARE LOCATED IN THE SERVICE FACTS. TO CHANGE AIRFLOW USE
THE MENU/OPTIONS BUTTONS.
4. LINE CHOKE AND WIRE BK/28 ONLY USED ON MODELS WITH 1 HP MOTORS.
5. FLAME SENSE TEST PADS: 1 VDC = 1 MICROAMP. FLAME CURRENT CAN VARY DEPENDING ON THE VOM THAT IS USED
AND THE VOLTAGE SUPPLIED TO THE FURNACE.
THE ACCEPTABLE RANGE IS 0.75-3 MICROAMPS.
6. IF APPLICABLE CONNECTION FOR FACTORY
PROGRAMMING ONLY.
FLAME_ROLLOUT1
YL/50
TO BURNER
FLAME_ROLLOUT2
BOX HARN
YL/50
YL/48
1
1
YL/49
2
2
THERMAL_LIMIT
YL/49
PS
YL/45
GAS
RAF-1
RAF-2
VALVE
MV C
YL/44
TNS
BL/2
WH/15
24v
120v
RD/6
BK/14
SEE
NOTE 4
LINE CHOKE
BK/28
BK/27
3
2
LINE
3 2 1
SEE NOTE 5
FP
FP
10
YL/3
HLI
9
RD/9
MV
8
7
GND
MENU OPTION
RD/6
6
TH
BL/5
5
MVC
YL/52
4
HLO
OR/11
3
PS
BL/2
2
TR
1
ILI (NOT USED)
FLAME_PROBE
WH/12
IFC
BK BLACK
LINE
FACTORY
WH WHITE
24 V
WIRING
YL YELLOW
ALTERNATE
OR ORANGE
GR GREEN
BR BROWN
LINE
FIELD
RD RED
WIRING
24 V
BL BLUE
IGN HOT SURFACE
FUSE
IGNITER
RAF REVERSE
LC LINE CHOKE
AIR FLOW
PS PRESSURE
GROUND
** INTERNAL THERMAL PROTECTION
SWITCH
1 Stage Inducer with CTM Blower Motor
Status Codes
COF
Blower Tap for Continuous Fan
IdL
Idle
COP C1.
Blower Tap for Compressor Mode
Ht
Heating
HtP H1.
Blower Tap for Heating Mode
tP
Blower Tap Number
rUn
Run Test Mode
COF
Continuous Fan
Error Codes
CP1
Cooling/Heat Pump Mode
E01
Loss of IRQ or internal failures
dft
Defrost Mode
E2.1
Retry exceeded (Failed to est flame)
Menu Options
E2.2
Recycles exceeded (loss of
established flame or PS open x10)
Orn
Orientation
Err
Active Alarm Menu
E2.3
Gas Valve not energized when it
L6F
Last 6 Faults (To Clear,
should be exceeded after 10 times
Hold Option Button 5 sec)
E3.1
Shorted Pressure Switch
Cr
Code Release Number
E3.2
Open Pressure Switch
COd
Cooling Off Delay (sec)
E04
Open Thermal Limit, Rollout Switch,
or Reverse Airflow Switch
HOd
Heat Off Delay (sec)
A801X-SVX001-1A-EN
A801X
ALTERNATE WIRING DIAGRAM - BLOWER MOTOR
BL/90
1
C
BK/85
L
2
BLOWER
GR/BK/91
G
3
MOTOR
WH/83
N
4
BLOWER
HOUSING
SEE NOTE 6
YL/48
GND
RD/WH/88
YL/WH/86
BL/WH/87
BK/WH/84
YL/51
OR/WH/89
1
2
3
4
5
6
7
8
9
10
11
12
BLOWER
YL/51
HOUSING
COM
GND
BK/39
L
1
®
REGAL -ENSITE
G
2
BLOWER
WH/40
N
3
MOTOR
YL/45
YL/43
RD/WH/35
YL/WH/36
BL/WH/37
BK/WH/38
OR/WH/55
120v 60 Hz. 1 PH
POWER SUPPLY PER LOCAL CODE
1
2
3
4
5
6
7
8
9
10
11
12
JUNCTION BOX
1
2
3
4
5
6
7
8
9
10
11
12
X
BK/30
2
2
1
1
PANEL LOOP
WH/17
1
4
3
2
1
BUTT SPLICE-WITH HEAT SHRINK
NEUTRAL
SEE NOTE 1
1
1
S1
2
4 3
2
1
2
3
1
S2
2
BUTT SPLICE-WITH HEAT SHRINK
SEE NOTE 1
IGN-N
WH/21
4
WH/21
IND-N
WH/20
3
BK/18
BK/22
IND-H
2
BK/22
IGN-H
1
RD/WH/23
TAP1
1
YL/WH/24
TAP2
2
BL/WH/25
TAP3
3
BK/WH/26
TAP4
4
INTEGRATED FURNACE CONTROL
OR/WH/56
TAP5
5
BL/57
GND
6
ELECTRICAL RATING
INPUT: 24VAC, 60 HZ.
H
LINE
TNS SEC. CURRENT: 450MA.
N
NEUTRAL
+ MV LOAD
GND GROUND
MV OUTPUT: 1.5A @ 24 VAC
HLO HIGH LIMIT
IND OUTPUT: 2.2 FLA, 3.5 LRA
OUTPUT
@120 VAC
HLI
HIGH LIMIT
IGN OUTPUT: 2.0 A @ 120 VAC
INPUT
CIRC. BLOWER OUTPUT:
PS
PRESSURE SWITCH
14.5 FLA, 25 LRA @ 120 VAC
W R G B/C Y/Y1
INPUT
HUMIDIFIER & AIR CLEANER
THERMOSTAT
IND
INDUCER
(DRY CONTACTS)
SEE NOTE 2
IFC
INTEGRATED
MAX. LOAD: 1.0A @ 120VAC
FURNACE
24 VAC OR 120 VAC MAY BE
CONTROL
USED
RAF REVERSE
FUSE: 5A
AIR FLOW
TIMINGS
FRS FLAME ROLLOUT
TH
24VAC (HOT)
PREPURGE: 0 SEC.
SWITCH
TR
24VAC (COMMON)
INTERPURGE: 60 SEC.
MVC MAIN VALVE
POST PURGE: 5 SEC.
COMMON
IGN WARMUP: 20 SEC.
FP FLAME PROBE
MV
MAIN VALVE
IAP: 3; TFI: 5 SEC.
TNS TRANSFORMER
RETRIES: 2 RECYCLES: 10
ILI
INDUCER LIMIT
HEAT ON DELAY: UP TO 30 SEC.
INPUT
COOL ON DELAY: 0 SEC.
IGN IGNITER
AUTO RESTART: 60 MIN.
FP
FLAME PROBE
AUTO RESTART PURGE: 60 SEC.
E05
Flame detected, should not be present
Voltage reversed polarity
E6.1
Bad Grounding
E6.2
(1) Igniter relay fails
E6.3
(2) Igniter open
Gas valve is energized whenit should be off
E7.1
E08
Flame current is low, but still
strong enough to allow operation
E11
(1) Gas valve not energized
(2) Gas valve relay stuck closed
E12
Open fuse
D346340P01 REV H
120v 60 Hz. 1 PH
POWER SUPPLY PER LOCAL CODE
JUNCTION BOX
H
N
GND
5
4
3
2
1
IFC
3
BK
LINE-H
2
BK
CIRC-H
TNS-H
1
BK
TNS-N
4
WH
3
WH
CIRC-N
BL/42
6
WH
LINE-N
1
5
4
IGN-H
1
BK
3
2
BK
IND-H
2
3
WH
IND-N
1
WH
IGN-N
4
1
RD/WH
TAP1
TAP2
2
YL/WH
3
BL/WH
TAP3
4
BK/WH
TAP4
TAP5
5
OR/WH
6
BL
GND
H
N
GND
1
ILI
2
BL
TR
X
OR
X
X
PS
3
4
YL
HLO
MVC
5
BL
6
RD
TH
7
GR
GND
RD
MV
8
9
HLI
BK/13
10
WH
FP
BK/29
VENT
W R G B/C Y/Y1
MOTOR
THERMOSTAT
(INDUCER)
**
FLAME_ROLLOUT2
THERMAL_LIMIT
YL
1
2
RAF-2
RAF-1
IGN
YL
YL
PS
FLAME_ROLLOUT1
YL
A801X
LINE CHOKE
PANEL LOOP
BK
1
BK
1
BK
2
2
N
BLOWER
WH
HOUSING
G
VENT
1
GND
MOTOR
L
2
BK
(INDUCER)
3
**
®
REGAL
ENSITE
IGN
BLOWER
WH
--------
HOUSING
BLOWER
BK
GND
MOTOR
RD/WH
1
YL/WH
2
BL/WH
3
BK/WH
4
OR/WH
5
BL
COM
TNS
WH
24v
120v
BK
BURNER
RD
MV
BOX GND
C
BL
GAS
VALVE
YL
YL
DEFAULT BLOWER MOTOR TAP SELECTIONS
OR
COF (CONSTANT FAN): TAP 1
COP (COOLING / HP): TAP 7
HT ( GAS HEAT): TAP 5
YL
N
TO: IFC CIRC-N-3 WH
G
GR/BK
L
TO: LINE CHOKE BK
C
TO: IFC GND-6 BL
ALTERNATE
-------
BLOWER
MOTOR
TO: IFC TAP1-1 RD/WH
1
TO: IFC TAP2-2 YL/WH
2
TO: IFC TAP3-3 BL/WH
3
TO: IFC TAP4-4 BK/WH
4
TO: IFC TAP5-5 OR/WH
5
15