Panasonic GT32-R User Manual page 133

Programmable display
Table of Contents

Advertisement

For GT02, GT02L, GT03-E, GT05, GT12, GT32, GT32-R and GT32-E
Code No.
Content
**0000
BCC error
**00FF
Time up error
Keyboard screen data
**0100
parts digit error
**0101
Alarm history error
True Type font file
**0102
transfer error
**0500
Tool setting error
SD memory card not
**1000
inserted
SD memory card
**1001
writing error
SD memory card
**1002
memory full
SD memory card
**1003
reading error
SD memory card data
**1004
error
SD memory card
**1005
saved file name error
SD memory card
**1006
recognition error
PLC model unmatch
**1020
error
PLC model
**1021
unsupported error
Password protection
**1022
error
Master memory
**1023
installation error
Program memory
**1024
shortage
Cause and solution
1) The value of BCC may be incorrect. Check if there is no
calculation mistake.
2) There is a temporary error due to noise, etc. Re-supply power
to the PLC and GT.
1) The PLC connection cable is disconnected. Check the
connection cable to make sure it is connected.
2) There is a temporary error due to noise, etc. Re-supply power
to the PLC and GT.
Check if the digit of the data parts on the keyboard screen has
been set correctly.
When updating the alarm history display is stopped, alarm
history data displayed on the GT's screen has been updated
within the memory. Once the stop of display update is cancelled,
new data is displayed.
Screen data is not transferred correctly. Re-transfer after
deleting all data.
The device that cannot be used is specified for the data. Check
if the used device is correct. (e.g. the word device is set in the
bit area.)
The SD memory card is not inserted to the SD memory card slot
properly. Check the SD memory card slot.
Data cannot be written to the SD memory card. Check whether
the SD memory card is not write-protected.
Data cannot be written as the memory of the SD memory card
has been exhausted. Delete some data in the SD memory card
or prepare a new SD memory card.
The data in the SD memory card cannot be read.
Check whether the saved data in the SD memory card is not
damaged with a PC.
The data loaded from a SD memory card does not match the GT
type. Read the data in the SD memory card with GTWIN, and
check whether it is not damaged.
The file name to be saved to the SD memory card from the GT
is not specified properly. Specify the file name properly.
The SD memory card cannot be recognized.
Check the SD memory card used.
Check if the PLC program for transfer matches the destination
PLC.
The selected PLC model is not supported. Confirm the PLC
model.
(1) Incorrect passwords were input three times or more. Input
the correct password after turning the power supply off and then
on again.
(2) The upload protection has been set for the PLC.
(3) The number of digits was changed when setting a new
password with the FP monitor function. Cancel the password
setting first to change the number of digits.
A master memory is installed in the PLC (FP-X).Programs
cannot be transferred to the PLC with the master memory from a
SD memory card.
Program memory shortage in the destination PLC. Decrease the
program size using the PLC tool.
5-11

Advertisement

Table of Contents
loading

Table of Contents