Requirements Specific To Solid-Walled Cabinets; Requirements Specific To Standard Open Racks; Cable Management Guidelines - Cisco 5000 Series Hardware Installation Manual

Platform and switch
Hide thumbs Also See for 5000 Series:
Table of Contents

Advertisement

Appendix A
Cabinet and Rack Installation
S e n d d o c u m e n t a t i o n c o m m e n t s t o n e x u s 5 k d o c s @ c i s c o . c o m
A perforated cabinet that conforms to these requirements is available from Rittal Corporation:

Requirements Specific to Solid-Walled Cabinets

A solid-walled cabinet is defined here as a cabinet with solid front and rear doors and solid side walls.
In addition to the requirements listed in the
page

Requirements Specific to Standard Open Racks

In addition to the requirements listed in the
page
the following requirements:

Cable Management Guidelines

To help with cable management, you might want to allow additional space in the rack above and below
the chassis to make it easier to route as many as 56 fiber or copper cables through the rack.
OL-15902-01
Rittal Corporation
One Rittal Place
Springfield, OH 45504
Contact: (800) 477–4220
Cabinet P/N: Rittal 9969427
Cabinet description: PS-DK/OEM Cabinet Assembly, (78.7 in.) 1998 mm X 23.6 in. (600 mm) X
39.4 in. (1000 mm) (H x W x D) (42 RU)
A-1, solid-walled cabinets must meet the following requirements:
A roof-mounted fan tray and an air cooling scheme in which the fan tray pulls air in at the bottom
of the cabinet and exhausts it out the top, with a minimum of 500 cubic feet per minute of airflow
exiting the cabinet roof through the fan tray.
Nonperforated (solid and sealed) front and back doors and side panels so that air travels predictably
from bottom to top.
A recommended cabinet depth of 36 to 42 inches (91.4 to 106.7 cm) to allow the doors to close and
for adequate airflow.
A minimum of 150 sq. inches (968 sq. cm) of open area at the floor air intake of the cabinet.
The lowest piece of equipment should be installed a minimum of 1.75 inches (4.4 cm) above the
floor openings to prevent blocking the floor intake.
A-1, if mounting the chassis in an open rack (no side panels or doors), ensure that the rack meets
The minimum vertical rack space per chassis must be two RU (rack unit), equal to 3.47 inches (8.8
cm).
The horizontal distance between the chassis and any adjacent chassis should be 6 inches (15.2 cm),
and the distance between the chassis air vents and any walls should be 2.5 inches (6.4 cm).
"This section includes the following topics:" section on
"This section includes the following topics:" section on
Cisco Nexus 5000 Series Hardware Installation Guide
Cable Management Guidelines
A-3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nexus 5500Nexus 5000 series

Table of Contents