Requirements Specific to Solid-Walled Cabinets

Reference Perforated Cabinet
A perforated cabinet that conforms to the above requirements is available from Rittal Corporation:
Rittal Corporation One Rittal Place Springfield, OH 45504
Phone: (800) 477-4000
Cabinet P/N: Rittal 9969427
Cabinet description: PS-DK/OEM Cabinet Assembly, 1998 x 600 x 1000 (H x W x D) (42U)
Requirements Specific to Solid-Walled Cabinets
In addition to the requirements listed in the General Requirements for Cabinets and Racks section, solid-walled
cabinets must meet the following requirements:
• The rack must have a roof-mounted fan tray and an air-cooling scheme in which the fan tray pulls air in
• The front and rear doors, and side panels, must be installed and nonperforated so that air flows predictably
• The overall cabinet depth should be 36 to 42 in. (91.4 to 106.7 cm) to allow the doors to close and to
• The open area of the floor air intake must be a minimum of 150 sq. in. (968 sq. cm).
• The lowest piece of equipment should be installed at a minimum of 1.75 in. (4.4 cm) above the floor
Cisco MDS 9396V Multilayer Fabric Switch Hardware Installation Guide
14
at the bottom of the cabinet and sends it out from the top, with a minimum airflow of 849.5 m
the cabinet roof through the fan tray, should be available.
from bottom to top.
facilitate adequate airflow.
openings to prevent blocking the floor intake.