McQuay MQS-174018-CFC216A Installation And Operation Manual page 15

Dc inverter floor ceiling type unit
Table of Contents

Advertisement

Model
MQIU-174018-HCU216A
MQIU-174024-HCU216A
MQIU-174036-HCU216A
MQIU-174048-HCU216A
MQIU-174060-HCU216A
Notes:
①. The fuse is located on the main board.
②. Install the disconnect device with a contact gap of at least 3 mm in all poles
nearby the units (Both indoor unit and outdoor unit).The appliance must be
positioned so that the plug is accessible.
③. The specifications of the breaker and power cable listed in the Table above
are determined based on the maximum power (maximum amps) of the unit.
④. The specifications of the power cable listed in the Table above are applied to
the conduit-guarded multi-wire copper cable (like, YJV copper cable,
consisting of PE insulated wires and a PVC cable jacket) used at 40°С and
resistible to 90°С(see IEC 60364-5-52). If the working condition changes, they
should be modified according to the related national standard.
⑤. The specifications of the breaker listed in the Table above are applied to the
breaker with the working temperature at 40°С. If the working condition
changes, they should be modified according to the related national standard.
⑥. Take 2 pieces of power cord of 0.75 mm
indoor and outdoor unit, with their longest lengths of 50m. Please select the
appropriate line length as per the actual installation conditions. The
communication lines can not be twisted together. For the unit (≤24K), it's
recommended to use 8m long communication line.
⑦. Take 2 pieces of power cord of 0.75mm
the wired controller and the indoor unit, with their longest lengths of 30m.
Please select the
conditions. The communication lines can not be twisted together. It's
recommended to use 8m long communication line.
⑧. The wire size of the communication line should be no less than 0.75 mm
recommended to take 0.75 mm
Table 3.5
Power
Supply
220-240V~ 60Hz
appropriate line length as per the actual installation
DC Inverter U-match Series Floor Ceiling Type Unit
Capability of Air
Switch(A)
16
20
25
40
40
2
as the communication lines between
2
as the communication lines between
2
power cords as the communication line.
13
Minimum Sectional Area
Of Earth Wire (mm
1.5
2.5
2.5
6.0
6.0
2
. It's
2
)