Bif-Con - Mitsubishi Electric AE630-SW Instruction Manual

Low-voltage air circuit breakers type ae, modbus interface unit bif-md
Hide thumbs Also See for AE630-SW:
Table of Contents

Advertisement

The measurement specifications of BIF-MD are shown in table 2.4.
Refer to Section 5.6 for details.
Table2.4 measurement items specification of BIF-MD
Item
Load current
Earth Leakage current
2) 5)
Line
1) 5)
Voltage
Phase
Active
1) 5)
Power
Reactive
Apparent
1) 5) 8)
Power factor
Active
1)
Energy
Reactive
1)
RMS
Harmonics current
(Max 19th)
Distortion
1)
Frequency
LTD/STD/INST
Fault current
GFR
ER
■1): These items cannot be metered when VT unit (VT) is not equipped.
■2): The leakage current metering is available only when the Optional setting module type is E1 (Earth leakage protection).
■3): Include the accuracy of ZCT.
■4): When using at 3φ3W system, the apparent power is calculated by (√3/2)×(I1×V12+ I3×V23).
Therefore, the accuracy may not be ensured in the unbalanced circuit.
■5): Rated voltage of measurement is 440V. Rated power and energy of measurement is √3×In×440V.
Rated earth leakage current of measurement is IΔn_max (=10A). Rated power factor is 90 degrees.
■6): Accuracy and cut off are defined as percentage of rated value.
■7): Accuracy is defined as percentage of true value.
■8): Power factor is measured for only fundamental wave. A waveform distortion is not included for power factor calculation.
2.2 BIF-CON (Option)
The general specifications of BIF-CON are shown in table 2.5.
Table 2.5 General specifications of BIF-CON
Item
Type name
Power supply
Number of channel
Digital input
Isolation
Signal level
Number of channel
Digital output
Isolation
Contact capacity
External dimensions
Operating ambient temperature
Storage ambient temperature
Operating/Storage ambient humidity
Operating/Storage ambience
Operating altitude
Installation
■1): SHT (AC380-500V) cannot be used.
Measurement Range
0 to 2×In [A]
0 to 2×IΔn_max [A]
0 to 725[V]
0 to 420[V]
-√3×(2xIn[A])×725 [V]
to +√3×(2xIn[A])×725 [V]
-√3×(2xIn[A])×725 [V]
to +√3×(2xIn[A])×725 [V]
4)
0 to +√3×(2xIn[A])×725 [V]
-50 [%] to 100 [%] to +50 [%]
0 to 99999999 [kWh]
0 to 99999999 [kvarh]
0 to 2×In [A]
0 to 200 [%]
45 to 65 [Hz]
0 to 20×In [A]
0 to 2×In [A]
0 to 2×IΔn_max [A]

BIF-CON

Supplied from BIF-MD
3 channels (INPUT1, INPUT2, INPUT3, general use)
Photo coupler isolation
12VDC, 30mA
3 channels (*SHT
1)
/CC/MD exclusive use)
Relay isolation
8A at 250V AC・DC (resistive load)
100(H) x 90(W) x 65(D)
-5 to +40℃ (However, the average of temperature per 24hours must not exceed +35℃)
-20 to +60℃ (However, the average of temperature per 24hours must not exceed +35℃)
max. 85%RH (no condensation) at the max. +40℃ in the clean air conditions.
Do not use and store in atmospheres with sulfide gas, ammonia gas, etc.
(H
S≤ 0.01ppm, SO
≤ 0.1ppm, NH
2
2
max. 2000m (6600ft.)
35mm IEC rail/Bracket
E-7
Unit
In < 500A : [0.1A]
In ≥ 500A : [A]
[0.1A]
[V]
In < 1000A : [0.1kW]
In ≥ 1000A : [kW]
In < 1000A : [0.1kvar]
In ≥ 1000A : [kvar]
In < 1000A : [0.1kVA]
In ≥ 1000A : [kVA]
[0.1%]
[kWh]
[kvarh]
In < 500A : [0.1A]
In ≥ 500A : [A]
[0.1%]
[Hz]
[10A]
[A]
[0.1A]
Specifications
1)
≤ 0.25ppm)
3
Accuracy
Cut off
6)
6)
±2.5%
2.0%
±15%
3) 6)
3.0%
6)
6)
±2.5%
10V
6)
6)
±2.5%
2.0%
6)
6)
±2.5%
2.0%
6)
6)
±2.5%
2.0%
6)
±5.0%
-
7)
6)
±2.5%
0.4%
7)
6)
±2.5%
0.4%
6)
2.0%
6)
±2.5%
-
7)
±2.5%
-
7)
±20%
-