Mitsubishi Electric AE630-SW Instruction Manual page 26

Low-voltage air circuit breakers type ae, modbus interface unit bif-md
Hide thumbs Also See for AE630-SW:
Table of Contents

Advertisement

Table 5.6.12 analog measurement 1 register
Address
Number
Access
of bytes
Dec.
Hex.
768
0300h
2
R
769
0301h
2
R
770
0302h
2
R
771
0303h
2
R
772
0304h
2
R
773
0305h
2
R
774
0306h
2
R
775
0307h
2
R
776
0308h
2
R
777
0309h
2
R
778 030Ah
2
R
779 030Bh
2
R
780 030Ch
2
R
781 030Dh
2
R
782 030Eh
2
R
783 030Fh
2
R
784
0310h
2
R
785
0311h
2
R
786
0312h
2
R
787
0313h
2
R
788
0314h
2
R
789
0315h
2
R
790
0316h
2
R
791
0317h
2
R
792
0318h
2
R
793
0319h
2
R
794 031Ah
2
R
795 031Bh
2
R
796 031Ch
2
R
797 031Dh
2
R
798 031Eh
2
R
799 031Fh
2
R
800
0320h
2
R
801
0321h
2
R
802
0322h
2
R
803
0323h
2
R
804
0324h
2
R
805
0325h
2
R
806
0326h
2
R
807
0327h
2
R
808
0328h
2
R
809
0329h
2
R
810 032Ah
2
R
811 032Bh
2
R
*1 Only data of current (from 300h to 308h) and earth leakage (032Ah, 032Bh) can be monitored without VT unit.
*2 In case of 3φ3W, N Pole measurements ( 303h, 308h, 30Eh to 310h) can not be monitored.
*3 Earth leakage (32Ah, 32Bh) can not be monitored without E1 module.
*4 *1 In case of "In=250 to 315", Unit: 0.1A. In case of "In=500 to 6300", Unit: 1A.
*5 In case of "In=250 to 630", Unit: 0.1kW, 0.1kvar, 0.1kVA. In case of "In=1000 to 6300", Unit: 1kW, 1kvar, 1kVA.
*6 Minus data is expressed as two's complement.
*7 In case of "LTD, STD, INST", Unit: 10A.
Fault cause can be monitored with Alarm and trip information (0252h).
*8 In case of "UVT", Data: non (0).
Register Name
Instantaneous current in Phase 1 (I1) *1
Instantaneous current in Phase 2 (I2) *1
Instantaneous current in Phase 3 (I3) *1
Instantaneous current in Pole N (IN) *1,2
Reserved
Demand current in Phase 1 (I1) *1
Demand current in Phase 2 (I2) *1
Demand current in Phase 3 (I3) *1
Demand current in Pole N (IN) *1,2
Reserved
Instantaneous voltage in Line 1-2 (V12)
Instantaneous voltage in Line 2-3 (V23)
Instantaneous voltage in Line 1-3 (V13)
Reserved
Instantaneous voltage in Phase 1-N (V1N) *2
Instantaneous voltage in Phase 2-N (V2N) *2
Instantaneous voltage in Phase 3-N (V3N) *2
Reserved
Reserved
Reserved
Reserved
Instantaneous power Factor *6
Instantaneous frequency
Reserved
Reserved
Reserved
Instantaneous active power *6
Reserved
Reserved
Reserved
Demand active power
*6
Reserved
Reserved
Reserved
Instantaneous reactive power *6
Reserved
Reserved
Reserved
Instantaneous apparent power
Demand reactive power *6
Demand apparent power
Instantaneous earth leakage (Ig) *1,3
Demand earth leakage (Ig) *1,3
Fault current *8
In case of "GFR", Unit: 1A.
E-26
Unit
Range
*4
*4
V
V
0.1%
Refer to table 2.4
Hz
*5
*5
*5
*5
*5
*5
0.1A
0.1A
*7
In case of "ER", Unit: 0.1A.

Advertisement

Table of Contents
loading

Table of Contents