Resister Address - Mitsubishi Electric AE630-SW Instruction Manual

Low-voltage air circuit breakers type ae, modbus interface unit bif-md
Hide thumbs Also See for AE630-SW:
Table of Contents

Advertisement

5.6 Resister address

Table 5.6.1 Setting register
Address
Number
Access
of bytes
Dec.
Hex.
521
0209h
2
R/W
522
020Ah
2
R/W
523
020Bh
2
R/W
524
020Ch
2
R/W
525
020Dh
2
R/W
526
020Eh
2
R/W
527
020Fh
2
R/W
528
0210h
2
R/W
529
0211h
2
R/W
530
0212h
2
R/W
531
0213h
2
R/W
532
0214h
2
R/W
533
0215h
2
R/W
534
0216h
2
R/W
535
0217h
2
R
536
0218h
2
R
537
0219h
2
R
538
021Ah
2
R
539
021Bh
2
R
540
021Ch
2
R
541
021Dh
2
R
542
021Eh
2
R
543
021Fh
2
R
544
0220h
2
R
545
0221h
2
R
546
0222h
2
R
547
0223h
2
R
548
0224h
2
R
592
0250h
2
R
593
0251h
2
R
594
0252h
2
R
595
0253h
2
R
596
0254h
2
R
597
0255h
2
R
*1 Data range: 0/10/20/30/40/50/60/120/180/240/300/360/420/480/540/600/660/720/780/840/900/1200/1800
*2 R/W: Read and write register.
R : Read only register.
*3 E1 is needed
*4 AP is needed.
*5 G1 is needed.
*Addresses 02**h (0209h-02B9h) can be monitored even if internal transmission error has occurred.
Register Name
Demand time for power
Demand time for current
Reset memory
Reserve
Demand time for earth leakage
Date and Time (Year and month.)
(YY/MM, BCD code)
Date and Time (Day and hour.)
(DD/HH. BCD code)
Date and Time (Minute and second.)
(MM/SS. BCD code)
Contact output (ACB control)
Reserve
Reserve
Alarm holding method
Iep (earth leakage pre-alarm pickup current) *3
Tep (earth leakage pre-alarm delay time) *3
WS, WB
Ir
WM (In = 250A to 315A)
WM (In = 500A to 6300A)
nd
Ip2 (2
additional pre-alarm pick-up current) *4
nd
Tp2 (2
additional pre-alarm time) *4
Ip1 (pre-alarm pick-up current)
Reserve
WS, WB: Iu (uninterrupted current)
WM: IL (LTD pickup current)
TL (LTD time)
Isd (STD pickup current)
Tsd (STD time)
Ii (INST pickup current)
Ig (GFR pickup current) *5
IΔn (ER pickup current) *3
Tg (GFR time) *5
Te (ER time) *3
Characteristic bit data
NP (Neutral pole protection level)
In (CT rating)
Contact input
Alarm and trip information
ETR Self diagnosis
Main setting module type
Option setting module type
E-21
Range
Unit
0 to 1800 *1
0 to 1800 *1
Refer to table 5.6.3
0 to 1800 *1
Year: 00 to 99,
Month: 01 to 12,
Day: 01 to 31,
Hour: 00 to 23,
Minute 00 to 59,
Second: 00 to 59,
Refer to table 5.6.5
Auto reset: 0000h
Self - Holding: 0001h
0 (non) to IΔn
0(non) to 3000
50 to 100
0.625 x In to 1.0 x In
0.1A
0.625 x In to 1.0 x In
0(non) to 100
0(non) to 1350
0.1s
68 to 115
0(non) to 120
0(non) to 150
0(non) to 1000
0(non) to 500
200 to 1600
0(non) to 100
0(non) to 10
0(non) to 3000
0(non) to 3000
Refer to table 5.6.6
50 to 100
250 to 6300
Refer to table 5.6.4
Refer to table 5.6.2
Refer to table 5.6.7
WS: 1h, WB: 4h, WM: 5h
Non: 0h, AP: 1h,
G1: 2h, E1: 3h
s
s
s
mA
ms
%
A
%
%
%
S
%
ms
%
%
A
ms
ms
%
A

Advertisement

Table of Contents
loading

Table of Contents