Fixed Configuration AC PDU Wiring

This section contains a brief description of the 3-phase wiring for AC Delta and Wye configurations that
facilities electricians should understand.
AC Delta and AC Wye are both basically 200 to 240 VAC input power:
AC Delta 3-Phase Wiring
Figure 2-10
three internal 2.5-kW power modules in the rectifier, where it is converted into DC power (nominal 54.5
VDC, 46 ADC) and routed to the three load zones of the chassis.
The AC Delta PDU is shipped with a 14-foot (4.3-m) AC power cord with a 4-pin L15-30P plug.
OL-5802-09
AC Wye Power Cord Plug
"Fixed Configuration AC PDU Wiring" section on page 2-13
AC Delta 3-phase wiring is typically used in the United States, Japan, and other countries where the
phase-to-neutral voltage is approximately 120 VAC and 208 VAC phase to phase.
AC Wye 3-phase wiring is typically used in Europe and countries where each phase-to-neutral
voltage is approximately 220 VAC.
shows a PDU wired for AC Delta 3-phase power. As shown, input AC power is routed to
Cisco CRS Carrier Routing System 8-Slot Line Card Chassis Site Planning Guide
To AC outlet
"Line Card Chassis Specifications" section on page
AC Power Systems
3-1.
describes the 3-phase
2-13