Chapter 4
Troubleshooting the Installation
The following conditions must exists for a DC PEM to operate normally:
Follow these steps to help isolate a problem with a DC PEM:
Is the MISWIRE LED on?
Step 1
If the INPUT OK LED is off, verify that the PEM is fully seated in its bay, the
Step 2
ejector levers are flush with the PEM faceplate, and the captive screws are
secured.
Verify that the PEM circuit breaker switch is on.
Step 3
OL-13831-01
The PEM is fully seated in its bay and the ejector levers are secured.
DC-input power is within the required range is correctly connected to the
chassis PDU terminal connector blocks.
The circuit breaker on the PEM is switched on.
The green LEDs labeled OUTPUT OK and INPUT OK on the PEM are on,
and the amber LED labeled MISWIRE is off.
If yes, the source DC positive and negative cable leads are connected in
reverse order to the terminal connector block on the PDU. Power off the PEM
circuit breaker switch and reconnect the cable leads correctly.
If no, go to Step 2.
If the INPUT OK LED goes on, go to Step 6.
If the INPUT OK LED remains off, go to Step 3.
If yes, go to Step 4.
If no, switch the circuit breaker on.
If the INPUT OK LED remains off, go to Step 4.
If the INPUT OK LED goes on, go to Step 6.
Troubleshooting a DC Power Subsystem
Cisco XR 12406 Router Installation Guide
4-11