Honeywell Fire-Lite Alarms ACC-25/50 Instruction Manual page 111

Voice evacuation control panels
Table of Contents

Advertisement

MS-9600, MS-9200UDLS and MS-9200UD
if an addressable device programmed to Zone 35 is activated and no other devices are active,
the message programmed for Zone 35 will be generated over speaker circuit 3 on the ACC-
25/50ZS or ACC-25/50ZST. (Refer to Table D.5 on page 109).
Programmed to
Addressable Pull Station
if an addressable device (address 09 in example below) programmed to Zone 35 is activated
and a second addressable device (address 15 in example below) programmed to Zone 36 is
activated, the highest priority message programmed to either Zone 35 or Zone 36 (Message 3
in example below) will be generated over speaker circuits 3 and 4. (Table D.5 on page 109). If
an addressable device (address 21 in example below) programmed to Zone 32 is then acti-
vated, the highest priority message programmed to Zone 32, 35, or 36 (Message 1 in example
below) will be generated over all speaker circuits. (Table D.5 on page 109).
Programmed to
Addressable Pull Station
(address 09)
Programmed to
Addressable Pull Station
(address 21)
Programmed to
Addressable Pull Station
(address 15)
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
Zone 35
Message 3
Zone 35
Message 4
(lowest priority of the three)
Zone 32
Message 1
(highest priority of the three)
Zone 36
Message 3
(2nd highest priority of the three)
Programmed Activation by FACP
Speaker Circuit 3
activate
Speaker Circuit 1
Speaker Circuit 2
activate
Speaker Circuit 3
Speaker Circuit 4
Speaker Circuit 5
Speaker Circuit 6
Speaker Circuit 7
Speaker Circuit 8
activate
activate
111