S2 - Record Bypass Switch On Acc-25/50 Series Motherboard (Acc-Mcb) - Honeywell Fire-Lite Alarms ACC-25/50 Instruction Manual

Voice evacuation control panels
Table of Contents

Advertisement

Field Programming
Switch
Switch
Switch
1
2
3
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
1 CMD1 has the highest priority, CMD5 has the lowest priority.
2
Dual Zone operation directs a single message to either or both amplifier circuits (factory default setting)
3 AAM1 refers to the first ACC-AAM25 amplifier circuit and AAM2 refers to the second ACC-AAM25 amplifier
circuit.
4 Single Zone operation directs the same message to both amplifier circuits.
5 The factory default evacuation message (length = 17 seconds) must be re-recorded to fit into this time slot.
Switch 4 - used in conjunction with Switch 5 to select AC Loss Delay time.
Switch 5 - used in conjunction with Switch 4 to select AC Loss Delay time:
Switch 6 - used for All-Call Paging from Remote Microphone
Switch 7 - used to select audio panel configuration
Switch 8 - used to enable/disable transferring of Trouble Relay/CMD1 trouble contacts during
AC loss
2.4 S2 - Record Bypass Switch on ACC-25/50 Series
Motherboard (ACC-MCB)
This switch, when placed in the down position, prevents accidental erasure of stored voice mes-
sages. See "Record/Playback Button - Record Customized Messages" on page 64 for additional
information.
38

S2 - Record Bypass Switch on ACC-25/50 Series Motherboard (ACC-MCB)

Maximum
Length of
Mode
Each
CMD1
Message
Single
20 sec.
Message 1 to
Zone
AAM1 & 2
5
Single
15 sec.
Message 1 to
Zone
AAM1 & 2
5
Single
12 sec.
Message 1 to
Zone
AAM1 & 2
Table 2.7 Switch Settings for Message Control
4 OFF and 5 OFF = No AC Loss Delay - immediate reporting (factory default)
4 OFF and 5 ON = 6 hour delay
4 ON and 5 OFF = 2 hour delay
4 ON and 5 ON = not used (invalid setting)
OFF = disable All-Call paging during page from Remote Microphone (factory default
setting)
ON = enable All-Call paging during page from Remote Microphone
OFF = ACC-25/50 or ACC-25/50ZS
ON = ACC-25/50ZST
OFF = CMD1 & Trouble Relay contacts track the AC Loss Relay and transfer upon AC
loss condition
ON = Only the AC Loss Relay contacts will transfer upon AC loss condition
RECORD
UP Position = The stored digital voice message may be overwritten with
BYPASS
a new one.
RECORD
BYPASS
Down Position = The stored digital voice message can not be
overwritten (factory default setting).
Audio Signal Control
1
CMD2
CMD3
Message 2 to
Message 3 to
AAM1 & 2
AAM1 & 2
Message 2 to
Message 3 to
AAM1 & 2
AAM1 & 2
Message 2 to
Message 3 to
AAM1 & 2
AAM1 & 2
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
CMD4
CMD5
not used
not used
Message 4 to
not used
AAM1 & 2
Message 4 to
Message 5 to
AAM1 & 2
AAM1 & 2