Error code
Error type
Error 01
01(A)
Error 02
02(A)
Error 03
03(B)
Error 04
04(B)
Error 05
05(B)
Error 06
06(B)
Error 07
07(A)
Error 08
08(B)
Error 09
09(B)
Error 10
10(A)
Error 11
11(A)
Error 12
12(B)
Error 13
13(A)
5.3
5.3.1
64
Error codes on the OxyLogic LCD
(1)
Description
Tank fill takes too long; check water pressure or replace supply/drain valve (Port: 20/21).
Measured flow while supply solenoid was closed; check or replace supply solenoid (Port: 20).
Tank drain takes too long; clean drainpipe (clogged) or replace drain valve (Port: 21).
Filter pressure exceeded; clean or replace filters.
Level sensor shows deviating value; clean or replace level sensor(s) (Port: 5).
Conductivity sensor shows deviating value; clean or replace sensor (Port: 15).
Outdoor temperature sensor shows deviating value; check or replace sensor (Port: 1).
Supply temperature sensor shows deviating value; check or replace sensor (Port: 3).
No connection with thermostat or network (Modbus); check cables and parameters (Port: 16).
Error supply fan; check cables and fan (Port: 13).
Error exhaust fan; check cables and fan (Port: 14).
Cooling performance below minimum value; check recirculation pump (Port: 18) and water distribution.
System error.
(1)
Error type explanation:
-
A = system locked
-
B = maintenance required
Update firmware
Preparations
Requirements:
-
Windows laptop
-
UpdateTool *
-
SettingsTool *
-
Settings: Datafile with PCB settings*
-
Micro USB cable (A standard charger cable for mobile devices will not work.)
-
Ethernet cable