MPP Solar LV 6548 User Manual page 26

Solar inverter / charger
Table of Contents

Advertisement

AC output mode
*This setting is only
28
available when the inverter
is in standby mode (Switch
off).
Low DC cut-off voltage:
 If battery power is only
power source available,
inverter will shut down.
 If PV energy and battery
power are available,
inverter will charge
29
battery without AC
output.
 If PV energy, battery
power and utility are all
available, inverter will
transfer to line mode
and provide output
power to loads.
30
Battery equalization
31
Battery equalization voltage
33
Battery equalized time
When the inverter is operation in split phase application, set up
inverter to be operated in specific phase.
L1 for split phase:
L2 for split phase:
(180° phase difference)
24V model default: 22.0V
If self-defined is selected in program 5, this program can be set
up. Setting range is from 21.0V to 24.0V for 24V model and 42.0V
to 48.0V for 48V model. Increment of each click is 0.1V. Low DC
cut-off voltage will be fixed to setting value no matter what
percentage of load is connected.
Battery equalization
If "Flooded" or "User-Defined" is selected in program 05, this
program can be set up.
default: 58.4V
60min (default)
24
L2 for split phase:
(120° phase difference)
48V model default: 44.0V
Battery equalization disable
(default)
Setting range is from 48.0V to
62.0V. Increment of each click is
0.1V.
Setting range is from 5min to
900min. Increment of each click is
5min.