Download Print this page

Tyco DV-5A Red-E Cabinet Quick Start Manual page 7

Red-e cabinet integrated deluge fire protection package
Hide thumbs Also See for DV-5A Red-E Cabinet:

Advertisement

Solenoid Pressure Rating
0
300 psi solenoid (standard)
Size
in.
1
1 1/2
01
2
2
02
3
3
03
4
4
04
6
6
05
(168,3 mm)
8
8
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
The following Part Numbers (P/N) are
provided for standard cabinets with
integral control panel, built-in automatic
air supply, for example, air compressor
and controls for dry pilot actuation, and
galvanized pipe, nipples, and fittings.
DV-5
Red-E Cabinet with
a
Deluge System
Specify: Size (specify) DV-5
Cabinet with (specify actuation) system
trim, P/N (specify per Table D)
Note: Dry Pilot Actuation is provided
standard with a OL12516AC (1/6 HP)
Air Compressor and Auxiliary Air Tank
complete with one Model AMD-1 Air
Maintenance Device.
P/N 53 — X —X — XX — X — X — X — X
System
Type
Deluge Wet Pilot Actuation
Deluge Dry Pilot Actuation
Deluge Electric Actuation
Deluge Remote-Resetting
Deluge Remote-Resetting
Pressure-Reducing
1
DV-5
RED-E CABINET DELUGE SYSTEMS
A
PART NUMBER SELECTION
Special Order
The DV-5
vided as follows as part of a special
request cabinet configuration:
• Without the control panel
• Without built-in automatic air sup-
ply, for example, air compressor and
controls for dry pilot actuation
• With an optional air/nitrogen mainte-
nance device when ordered without
built-in automatic air supply for dry
pilot actuation
• With trim black pipe, nipples, and
fittings, as may be desired for AFFF
systems
• With special size air compressors
for dry pilot actuation as shown in
Table B
• With 50 Hz air compressors as
Red-E
shown in Table C
A
• With seismic kit. Kit must be ordered
separately.
Valve Size
1 1/2 to 4 in. . . . . . . . . . . . . . . 53-040-0-001
4 to 8 in. . . . . . . . . . . . . . . . . . 53-080-0-001
Air Maintenance
Device
2
0
None
1
AMD-1
2
AMD-2
3
AMD-3
1. Deluge Remote-Resetting, Pressure-Reducing available in sizes
3 to 8 in. (DN80 to DN200).
2. Air Maintenance Device does not apply (select "0" - None) when a
Compressor (1-8) is selected.
3. Black trim types are available only on request. Contact Red-E
Cabinet Technical Support for information.
4. A 50 Hz compressor model is available on request, select the
equivalent horsepower rating (1-8).
TABLE D
Red-E Cabinet can be pro-
A
Part No.
Control
Panel
0
None
0
A
Included
1
2
3
4
Trim
Type
3
5
1
NPT Galvanized
6
7
* Requires 230V/60Hz
Options
The DV-5
Red-E Cabinet can be pro-
A
vided with the following options:
• With sight flow gage (provides a
visual indication of flow through the
main drain)
• With extra capacity batteries
(12V up to 18Ah) for longer battery
time and/or systems with heavy
power requirements, for example,
numerous audible signaling devices
• With Class "A" initiating appliance
circuits
• This option permits the connection
of Class "A" style wiring to the initi-
ating zones
• With Class "A" indicating appliance
circuits
• This option permits the connection
of Class "A" style wiring to the indi-
cating zones
• With auxiliary relay modules to
provide extra dry contacts when
required; up to an 8 ARM-44 module
per cabinet can be added
• W i t h
R A - 4 410
Annunciator
Contact Red-E Cabinet Technical
Support for information about special
request cabinet configurations.
TFP1301
Page 7 of 8
Compressor
2,4
None
1/6 hp 120 Gal
1/3 hp 250 Gal
1/2 hp 400 Gal
3/4 hp 430 Gal
1 hp 615 Gal
1 1/2 hp 915 Gal
2 hp 1225 Gal*
R C
R e m o te

Advertisement

loading

This manual is also suitable for: