Download Print this page
Tyco DV-5A Red-E Cabinet Quick Start Manual

Tyco DV-5A Red-E Cabinet Quick Start Manual

Red-e cabinet integrated deluge fire protection package
Hide thumbs Also See for DV-5A Red-E Cabinet:

Advertisement

Quick Links

DV-5A Red-E Cabinet
Integrated Deluge Fire Protection Package
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycofire/dv-5a-red-e-
cab-int-deluge-fire-pro-pack
General
Description
The TYCO DV-5
Red-E Cabinet is a
A
pre-assembled fire protection valve
package enclosed within a free-stand-
ing cabinet designed to occupy minimal
floor space and to provide an aestheti-
cally pleasing enclosure for a fire pro-
tection valve riser. The entire package
is pre-wired and the water inlet and
outlets to the valve riser are grooved to
provide minimal installation time. The
valve package includes the system
(manual) shut-off control valve, auto-
matic water control valve, and water-
flow/supervisory switches. When dry
pilot actuation is utilized, a built-in air
compressor with associated controls
provides an automatic air supply for
the dry pilot lines.
Integral to the DV-5
Red-E Cabinet is a
A
control panel and back-up batteries for
providing electrical alarm, supervisory,
and trouble functions. All switches
within the cabinet are pre-wired to the
Page 1 of 8
control panel, making the electrical
connections for power, detection cir-
cuits (as applicable), and alarms the
only remaining connections to com-
plete the system.
In addition to the control panel being
integral to the DV-5
Red-E Cabinet,
A
windows have been provided in the
door for viewing the releasing panel
functions and essential system pres-
sure gauges. A lock for the control
panel access door is standard, and a
lock for the cabinet door is optional.
Features and benefits are as follows:
• Aesthetically pleasing appearance
• Professionally assembled
• Internally wired
• Custom manufactured
• All gauges and panel display are
externally visible
• Industrial grade rollers (4) are stan-
dard at bottom of cabinet
• Fork lift compatible
• Two-door cabinet design for ease of
maintenance
• Internal, gauge panel, and control
panel lighting
• Optional seismic kit
The DV-5
Red-E Cabinet is designed
A
to readily incorporate 1-1/2 in. to 8 in.
(DN40 to DN200) valve risers for the fol-
lowing types of deluge systems:
• Wet Pilot Actuation
• Dry Pilot Actuation
• Electric Actuation
• Remote-Resetting
• Remote-Resetting,
*
Pressure-Reducing
*3 in. to 8 in. (DN80 to DN200)
NOTICE
The TYCO DV-5
Red-E Cabinets
A
described herein must be installed
and maintained in compliance with
this document and with the applica-
ble standards of the NATIONAL FIRE
PROTECTION ASSOCIATION (NFPA),
in addition to the standards of any
authorities having jurisdiction. Failure
to do so may impair the performance
of these devices.
JULY 2022
Worldwide
www.tyco-fire.com
Contacts
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Technical
Data
Approvals
UL and C-UL Listed System Types
• Wet Pilot Actuation
• Dry Pilot Actuation
• Electric Actuation
• Remote-Resetting
• Remote-Resetting, Pressure-Reducing
FM Approved and CSFM Listed
System Types
• Wet Pilot Actuation
• Dry Pilot Actuation
• Electric Actuation
System Types
The technical data sheets referenced in
Table A provide complete details for each
system type arrangement.
Working Pressure Range
DV-5
Valve: 20 to 300 psi (1,4 to 20,7 bar)
a
Valve Trim: Refer to individual trim techni-
cal data sheets for rated trim pressures as
shown in Table A
TFP1301

Advertisement

loading

Summary of Contents for Tyco DV-5A Red-E Cabinet

  • Page 1 Worldwide www.tyco-fire.com Contacts DV-5A Red-E Cabinet Integrated Deluge Fire Protection Package control panel, making the electrical IMPORTANT connections for power, detection cir- Refer to Technical Data Sheet cuits (as applicable), and alarms the TFP2300 for warnings pertaining to only remaining connections to com- regulatory and health information.
  • Page 2 TFP1301 Page 2 of 8 Nominal Riser Size Nominal Dimension in. (mm) Description 1 1/2 (DN40) 2 (DN50) 3 (DN80) 4 (DN100) 6 (DN150) 8 (DN200) System Discharge 1 1/2 (DN40) 2 (DN50) 3 (DN80) 4 (DN100) 6 (DN150) 8 (DN200) Supply Header 4 (DN100) 8 (DN200)
  • Page 3: Design Considerations

    TFP1301 Page 3 of 8 1 - Supply Header 2 - Drain Header 3 - Supply and Drain Header Connections on Left or Right Side 4 - System Discharge Connection 5 - DV-5 Valve with Deluge Trim 6 - Manual System Shut-Off Valve 7 - System Pressure Gauges 8 - Manual Control Station...
  • Page 4 TFP1301 Page 4 of 8 Description Model C-UL/ULC Automatic Water Control Valve and Deluge Trim Wet Pilot Actuation TFP1311 Dry Pilot Actuation TFP1316 DV-5 Electric Actuation TFP1321 Remote-Resetting TFP1325 Remote-Resetting, Pressure-Reducing TFP1326 System Shut-Off Valve, 1 1/2 to 2 in. (DN40 to DN50) POWERBALL System Shut-Off Valve, 3 to 8 in.
  • Page 5: Installation

    50 HZ AIR COMPRESSOR SELECTION CRITERIA FOR DELUGE DRY SYSTEM ARRANGEMENTS BASED ON SYSTEM TYPE AND VOLUME Installation Red-E Cabinet The TYCO Red-E Cabinet does not require any regularly scheduled inspec- Technical tion or maintenance. The riser com- The TYCO DV-5...
  • Page 6 TFP1301 Page 6 of 8 ELECTRICAL POWER CIRCUITS FROM BUILDING BREAKER PANEL ONE CIRCUIT FOR RELEASING PANEL (IF APPLICABLE) CAPABLE OF PROVIDING 120 VAC 60 Hz MAX. 165 VA OR 220 VAC 50/60 Hz 185 VA MAX. ADDITIONAL POWER CIRCUIT FROM BREAKER PANEL FOR AIR COMPRESSOR AS APPLICABLE DETECTION CIRCUITS...
  • Page 7 • With sight flow gage (provides a • Without the control panel For warranty terms and conditions, visit visual indication of flow through the www.tyco-fire.com. main drain) • Without built-in automatic air sup- ply, for example, air compressor and • With extra capacity batteries...
  • Page 8 TFP1301 Page 8 of 8 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 © 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;...

This manual is also suitable for:

Olr12016acOlr25033acOlr40050acOlr43075acOlr615100ac2Olr915150ac2 ... Show all