DV-5A Red-E Cabinet
Integrated Deluge Fire Protection Package
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycofire/dv-5a-red-e-
cab-int-deluge-fire-pro-pack
General
Description
The TYCO DV-5
Red-E Cabinet is a
A
pre-assembled fire protection valve
package enclosed within a free-stand-
ing cabinet designed to occupy minimal
floor space and to provide an aestheti-
cally pleasing enclosure for a fire pro-
tection valve riser. The entire package
is pre-wired and the water inlet and
outlets to the valve riser are grooved to
provide minimal installation time. The
valve package includes the system
(manual) shut-off control valve, auto-
matic water control valve, and water-
flow/supervisory switches. When dry
pilot actuation is utilized, a built-in air
compressor with associated controls
provides an automatic air supply for
the dry pilot lines.
Integral to the DV-5
Red-E Cabinet is a
A
control panel and back-up batteries for
providing electrical alarm, supervisory,
and trouble functions. All switches
within the cabinet are pre-wired to the
Page 1 of 8
control panel, making the electrical
connections for power, detection cir-
cuits (as applicable), and alarms the
only remaining connections to com-
plete the system.
In addition to the control panel being
integral to the DV-5
Red-E Cabinet,
A
windows have been provided in the
door for viewing the releasing panel
functions and essential system pres-
sure gauges. A lock for the control
panel access door is standard, and a
lock for the cabinet door is optional.
Features and benefits are as follows:
• Aesthetically pleasing appearance
• Professionally assembled
• Internally wired
• Custom manufactured
• All gauges and panel display are
externally visible
• Industrial grade rollers (4) are stan-
dard at bottom of cabinet
• Fork lift compatible
• Two-door cabinet design for ease of
maintenance
• Internal, gauge panel, and control
panel lighting
• Optional seismic kit
The DV-5
Red-E Cabinet is designed
A
to readily incorporate 1-1/2 in. to 8 in.
(DN40 to DN200) valve risers for the fol-
lowing types of deluge systems:
• Wet Pilot Actuation
• Dry Pilot Actuation
• Electric Actuation
• Remote-Resetting
• Remote-Resetting,
*
Pressure-Reducing
*3 in. to 8 in. (DN80 to DN200)
NOTICE
The TYCO DV-5
Red-E Cabinets
A
described herein must be installed
and maintained in compliance with
this document and with the applica-
ble standards of the NATIONAL FIRE
PROTECTION ASSOCIATION (NFPA),
in addition to the standards of any
authorities having jurisdiction. Failure
to do so may impair the performance
of these devices.
JULY 2022
Worldwide
www.tyco-fire.com
Contacts
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Technical
Data
Approvals
UL and C-UL Listed System Types
• Wet Pilot Actuation
• Dry Pilot Actuation
• Electric Actuation
• Remote-Resetting
• Remote-Resetting, Pressure-Reducing
FM Approved and CSFM Listed
System Types
• Wet Pilot Actuation
• Dry Pilot Actuation
• Electric Actuation
System Types
The technical data sheets referenced in
Table A provide complete details for each
system type arrangement.
Working Pressure Range
DV-5
Valve: 20 to 300 psi (1,4 to 20,7 bar)
a
Valve Trim: Refer to individual trim techni-
cal data sheets for rated trim pressures as
shown in Table A
TFP1301