9.5 Outdoor unit malfunction and protection codes
Error
/code
E1
Phase sequence error
E2
Indoor & outdoor unit communication error
Ambient temperature T4/pipe temperature T3
E4
sensor error
E5
Voltage error
E7
Discharge sensor error
E9
Eeprom error
H0
IR341 and MC9S08AC128 communication error
H1
0537 and MC9S08AC128 communication error
H4
Three times P6 protection in 60 minutes
H5
Three times P2 protection in 60 minutes
H6
Three times P4 protection in 100 minutes
H8
High pressure sensor error
H9
Three times P9 protection in 60 minutes
P0
Top temperature protection of compressor
High pressure protection or high temperature
P1
protection of discharge sensor
P2
Low pressure protection
P3
Over-current protection of compressor
P4
Discharge temperature protection
P5
Pipe temperature protection
P6
Inverter module protection
P9
DC fan module protection
L0
Inverter module error
L1
DC generatrix low voltage error
L2
DC generatrix high voltage error
L4
MCE error/ synchronization/ closed loop
L5
Zero speed protection
L7
Phase sequence error
Frequency difference in one second more than
L8
15Hz protection
Frequency difference between the real and the
L9
setting frequency more than 15Hz protection
Midea R410A Full DC Inverter Split Type Series Technical Manual
Content
Note
Discharge pressure less than or equal to 0.3MPa
Display H6, if three times in 100 minutes
Display H5, if three times in 60 minutes
Display H6, if three times in 100 minutes
Display H4, if three times in 60 minutes.
Display H9, if three times in 60 minutes