If the unit is installed where the flowing speed of air is high, such as on the exposed roof, the
measures including sunk fence and persian blinds can be taken, to prevent the turbulent flow
from disturbing the air entering the unit. If the unit needs to be provided with sunk fence, the
height of the latter should not be more than that of former; if persian blinds are required, the total
loss of static pressure should be less than the static pressure outside the fan. The space
between the unit and sunk fence or persian blinds should also meet the requirement of the
minimum installation space of the unit.
When carring the unit, the angle of inclination should not be more than 15º to avoid overturn of
the unit.
Rolling handling: several rolling rods of the same size are placed under the base of the unit, and
the length of each rod must be more than the outer frame of the base and suitable for balancing
of the unit.
Lifting; the strength lifting rope (or belt) can bear should be 4 times the weight of the unit. Check
the lifting hook and ensure that it is firmly attached to the unit, and the lifting angle should be
more than 60º . To avoid damages to the unit, the contact position of the unit and lifting rope
should be provided with an at least 50mm thick wood block, cloth or hard paper. Any person is
not allowed to stand below the unit when lifting it.