Installation space
The unit should be located on the horizontal foundation, the ground floor or the roof which can
bear operating weight of the unit and the weight of maintenance personnel.
If the unit is located so high that it is inconvenient for maintenance personnel to conduct
maintenance, the suitable scaffold can be provided around the unit.
The scaffold must be able to bear the weight of maintenance personnel and maintenance
facilities.
The bottom frame of the unit is not allowed to be embedded into the concrete of installation
foundation.
Damping devices must be provided between the unit and its foundation. By means of the
Ф15mm diameter installation holes on the steel frame of the unit base, the unit can be fastened
on the foundation through the spring damper. The damper does not go with the unit, and the user
can select the damper according to the relevant requirements. When the unit is installed on the
high roof or the area sensitive to vibration, please consult the relevant persons before selecting
the damper.
Installation steps of the damper:
Make sure that the flatness of the concrete foundation is within ± 3mm, and then place the
unit on the cushion block.
Raise the unit to the height suitable for installation of the damping device.
Remove the clame nuts of the damper
Place the unit on the damper, and align the fixing bolt holes of the damper with the fixing
31
A
≥1,500mm
≥2,000mm
B
C
≥2,000mm
MCAC-UTSM-201406
D
E
≥1,500mm
≥8,000mm