INSTALLATION MANUAL Split Duct Air Conditioner Thank you very much for purchasing our air conditioner, Before using your air conditioner, please read this manual carefully and keep it for future reference.
CONTENTS PAGE indoor unit, and direct the transmitting part of the remote controller to the receiver of the indoor unit. PRECAUTIONS..................1 The remote controller should be over 1m away from the ACCESSORIES ..................2 television or sound box. INSTALLATING INDOOR UNIT ...............2 Do not place the remote controller at a moist place, near the heat sources such as stove, or expose it directly in the sunlight.
13) Flare tool The site contains mineral oils such as cutting lubricant. 14) Pipe bender Seaside where the air contains much salt. 15) Level vial Hotpring area where corrosive gases exist, e.g., sulfide gas. 16) Metal saw Factories where the supply voltage fluctuates seriously. 17) Gauge manifold (Charge hose:R410A special requirement) Inside a car or cabin.
Page 5
3. INSTALLATING INDOOR UNIT Fix the pendant bolts firmly and reliably in light of the specific situation. 3.1 Installation Space(Unit:mm) Installation of the pendant bolt in different environments. Ensure enough space required for installation and maintenance. A. Wooden structure Put rectanglar sticks across the beams, and set pendant bolts. Wooden span Beam Maintenance space...
3.6 Dimension(Unit:mm) and sound insulation devices, especially in the noise-sensitive spaces such as meeting rooms. MHC-96HWD1N1(A) For connection of the flange plane, use non-flammable canvas adapter to prevent transmission of vibration. For its size, see the indoor unit outline diagram. Use M6X20 screws (configured on site) for connection.
Page 7
Lifting hook Hoisting rope (belt) In the lifting process, without removal of cartons and other packaging to avoid damage to the product appearance. Fig.4-2 Single unit installation (Wall or obstacle) Center of gravity Air inlet >300 Maintain the electric As shown illustrating the rope must wire and pipeline pass through the inside of the circle two wooden support stakes, to avoid...
Page 8
The indoor and outdoor connecting pipe interface and power NOTE line outlet Vavious piping and viring patterns can be selected,such as out from All the pictures in this manual are for explanation purpose only. the front ,the back the side ,and undersurface, etc.(The follow display They may be slightly different from the air conditioner you the locations of several piping and wiring knock-off interfaces) purchased(depend on model).The actual shape shall prevail.
Page 9
Vacuuming should be done from both liquid side and gas side simultaneously. φ φ 25.4mm 9.5mm MHC-96HWD1N1 ( A ) Open all valves. Allowed length of refrigerant pipe and height difference 4.13 Refrigerant Replenishment Quantity For one-way pipe whose length is no longer than 5m, please Outdoor unit refer to nameplate for refrigerant filling amount.No extra...
4.14 Schematic Diagram Of Connection b. Leakage detection alarm device linked Between Indoor Unit And Outdoor Unit with the mechanical ventilation device Signal wire Indoor unit a. Ventilation orifice part Gas-side connective pipe (The leakage detection alarm device should be installed at the place of system vulnerable to retention of the refrigerant) Fig.4-16...
Specifications of power supply Table.5-1 Indoor unit Outdoor unit Model MHC-96HWD1N1 ( A ) MOUA-96HD1N1-R Power 380-415V 3N~ 50Hz 220-240V~ 50Hz Switch capacity of the main 16/16 40/40 power suppliy/fuse(A) Indoor unit power cable(mm 3×2.5 mm includes grounded wire Outdoor unit power cable(mm 5×6.0 mm...
8. STATIC-CURVE heavy, it is necessary that two persons do it together. MHC-96HWD1N1 ( A ) 9.1 Steps to remove the fan motor assembly Static curve (ENC2) 0 1) Remove the screws around the base of air conditioner till the base can be removed.
Page 13
9.2 Steps to install the fan motor assembly 1) Lift the fan motor assembly; make the edges of fan motor assembly touch the guide rails. It needs to two persons. (Fig.9-7) 2) Hold the bottom of the assembly, and then push it up along the guide rails.
11. TRIAL RUN Indoor unit Please conduct in accordance with “Trial Run Tenor Nameplate” Check whether the switch of the remote controller or wire on the electric control box. controller is normal. Check whether the functional keys of the remote controller or wire controller are normal.
Page 16
11.2 Information requirements for air-to-air conditioners Cooling mode: Information requirements for air-to-air conditioners Model(s):MOUA-96HD1N1-R Test matching indoor units from1,Duct:MHC-96HWD1N1(A) Outdoor side heat exchanger of air conditioner:air Indoor side heat exchanger of air conditioner:air Type:compressor driven If applicable:driver of compressor:electric motor...
Page 17
Heating mode: Information requirements for air-to-air conditioners Model(s):MOUA-96HD1N1-R Test matching indoor units from1,Duct:MHC-96HWD1N1(A) Outdoor side heat exchanger of air conditioner:air Indoor side heat exchanger of air conditioner:air Idication if the heater is equipped with a supplementary heater:no If applicable:driver of compressor:electric motor...