Chiller Performance Data
This manual uses a typical 120-ton air-cooled chiller
consisting of four modules with brazed plate
evaporators for example purposes. The model number
Table 9. Typical Manhattan™ air-cooled chiller specification for example purposes
Chiller System (four 30-ton air-cooled chiller modules) Model # TPACVMV0300D4-MM
Evaporator Type
Evaporator Flow
Evaporator Fluid
Entering Fluid Temperature
Leaving Fluid Temperature
Evaporator Pressure Drop
Maximum Evaporator Operating
Pressure
Refrigerant
Chiller Modules (4)
Compressors
Horsepower
Locked Rotor Amps
System
Total Full Load Amps
Minimum Circuit Ampacity
Dimensions
Each Chiller Module
Weight
Each Chiller Module
Primary module is 46 in. wide, including power distribution panel.
(a)
(b)
Including power distribution panel and end louvers.
ARTC-SVX001B-EN
brazed plate
274 gpm
70/30 water/glycol
54 °F (12 °C)
44 °F (7 °C)
5.8 psi
650 psi (refrigerant side)
R410A
two per module
15
340 amps
492 amps
506 amps
39 W x 95 L x 87 H in.
(a)
2,500 lbs.
and a chiller's precise electrical and refrigerant data
can be found on the chiller model nameplate. See
"Model Number and Coding," p.
Condenser Type
Ambient Design Temperature
System Capacity
Connections
Rated Load Amps
Total Full Load Amps
Electrical Power Supply
Maximum Overcurrent Capacity
Fans (2 ECM type)
Overall Chiller System
Overall Chiller System
7.
copper tube aluminum fin
95 °F (35 °C)
1,2274,000 btu/hr. (106.2 tons)
6 in. roll grooved
46 amps each
123 amps per module
208/60/3
600 amps
5.7 amps each
156 W x 95 L x 87 H in.
(b)
10,000 lbs.
47
Need help?
Do you have a question about the Arctic Manhattan Gen II and is the answer not in the manual?