I I n n s s t t a a l l l l a a t t i i o o n n M M e e c c h h a a n n i i c c a a l l

Mounting Rails

The chiller must be positioned on a firm, level surface.
When modules are installed onto structural steel rails,
the rails must be level such that the modules are
properly aligned. Mounting rails must be a minimum of
4 inches wide. Custom modules may have different
requirements. Consult submittal drawings to confirm
dimensions. See
Figure 4, p.
Figure 4. Chiller installation on mounting rails
While the compressors are installed with rubber-in-
shear isolation pads, for additional vibration isolation,
spring isolators may be installed under the structural
steel mounting rails.
18
18.
All of the modules arrive with labels on the electrical
and control panel. Review the installation drawings to
determine which is the first, primary, module. Typically
the primary module also has the power distribution
panel attached to it. If part of the chiller system, the
tank and pump module must be installed last at the
opposite end of the chiller modules. (The power
distribution panel is typically installed on the tank and
pump module when so equipped.)
When installing modules directly onto a concrete pad,
rubber-in-shear isolator pads may be installed under
each module.
After setting each module, remove front or rear access
panels to improve access to components when making
connections.
ARTC-SVX001B-EN