Trane Arctic Manhattan Gen II Installation, Operation And Maintenance Manual page 70

Air-cooled modular chiller
Table of Contents

Advertisement

C C h h i i l l l l e e r r T T r r o o u u b b l l e e s s h h o o o o t t i i n n g g
Code (hex)
Fault / Aux. code
5691
Measurement circuit ADC
5692
PU board powerfail
5693
Measurement circuit DFF
5696
PU state feedback
5697
Charging feedback
6181
FPGA version incompatible
6306
FBA A mapping file
6481
Task overload
6487
Stack overflow
64A1
Internal file load
64B2
User set fault
64E1
Kernel overload
6581
Parameter system
65A1
FBA A parameter conflict
6681
EFB comm loss Programmable fault:
58.14 Communication loss action
70
Cause
Measurement circuit fault.
Power unit power supply failure.
Measurement circuit fault.
State feedback from output phases
does not match control signals.
Charging feedback signal missing.
Firmware and FPGA versions are
incompatible.
Fieldbus adapter A mapping file read
error.
Internal fault.
Internal fault.
File read error.
Loading of user parameter set failed
because
• requested set does not exist
• set is not compatible with control
program
• drive was switched off during
loading.
Operating system error.
Parameter load or save failed.
The drive does not have a
functionality requested by PLC, or
requested functionality has not been
activated.
Communication break in embedded
fieldbus (EFB) communication.
What to do
Contact your local ABB
representative.
Contact your local ABB
representative.
Contact your local ABB
representative.
Contact your local ABB
representative.
Check the feedback signal coming
from the charging system
Reboot the control unit (using
parameter
96.08 Control board boot) or by
cycling power. If the problem
persists, contact your local ABB
representative
Contact your local ABB
representative.
Reboot the control unit (using
parameter
96.08 Control board boot) or by
cycling power. If the problem
persists, contact your local ABB
representative
Reboot the control unit (using
parameter
96.08 Control board boot) or by
cycling power. If the problem
persists, contact your local ABB
representative
Reboot the control unit (using
parameter
96.08 Control board boot) or by
cycling power. If the problem
persists, contact your local ABB
representative
Ensure that a valid user parameter
set exists. Reload if uncertain.
Reboot the control unit (using
parameter
96.08 Control board boot) or by
cycling power. If the problem
persists, contact your local ABB
representative
Try forcing a save using parameter
96.07 Parameter save manually.
Retry.
Check PLC programming.
Check settings of parameter groups
50 Fieldbus adapter (FBA) and 51
FBA A settings.
Check the status of the fieldbus
master (online/offline/error etc.).
Check cable connections to the
EIA-485/X5 terminals 29, 30 and 31
on the control unit.
ARTC-SVX001B-EN