4.14

Gas feeding

Explosion danger due to fuel leaks in the pres-
ence of a flammable source.
Precautions: avoid knocking, attrition, sparks and
heat.
Make sure the fuel interception tap is closed be-
fore performing any operation on the burner.
The fuel supply line must be installed by qualified
personnel, in compliance with current standards
and laws.
WARNING

4.14.2 General gas feeding diagram (example)

D7543
Key (Fig. 26)
C
Vibration damping joint
GF
Gas filter
HPG High gas pressure regulator
LPG
Low gas pressure regulator
MM
Pressure gauge
PA
Minimum air pressure switch
PGM Maximum gas pressure switch
PGm Minimum gas pressure switch
RG
Gas butterfly valve
SRV
Pressure limiting valve with outlet into the environment
VE
Fan
VPS
Leak detection control device
VR
Gas pressure regulator solenoid valve
VS
Gas safety solenoid
20146011
Installation

4.14.1 Gas feed connection to the burner

Burner connection
The connection of the burner to the gas train is carried out using
the flange connection. The dimensions of the flange are given in
Fig. 8 on page 12.
Use the relative adapters to connect the gas flange to the train,
supplied as accessories.
PART THAT IS THE RESPONSIBILITY OF THE INSTALLER/USER
22
GB
max. 500 mbar
0.5 ÷ 4 bar
Fig. 26