Fault -- 23 To - TAS POWERTEK APFC-05 User Manual

Automatic power factor controller
Table of Contents

Advertisement

...continued.
Int Temperature Flt
Disable
:0
Temperature
Resume
: 55 Deg C
Temperature
Limit
: 65 Deg C
Step Health Chk
Disable : 0
Bank KVAR Fault
Tolerance
:10
Bank KW Fault
Tolerance
:10
TAS POWERTEK PVT.LTD.
Internal Temperature Fault: Unit monitors the
temperature inside the APFC 05 housing. This
temperature can go up either due to ambient temperature
in the APFC panel has gone up beyond limit or if some
component failure in APFC-05 hardware itself. Upper limit
is for tripping and lower limit is for normal operation
(resume).
• Step Health Check : APFC 05 carries out on line
monitoring of the kVAr values of every step. This is when
the step is put in the tolerance limit defined here is
exceeded, that specific bank is declared faulty.
VERSION 1.0
Updated on: FEB. 18, 2015