For Testing banks with manual ON / OFF commands:
Press ENTER key, the cursor will start blinking. Use keys
to select the specific bank/s that are healthy and use key to
turn ON and use key to turn OFF that capacitor banks.
To come out of Manual ON/OFF edit mode, press ENTER key so
that cursor stops blinking.
Edit Parameters:
This mode is used to carry out system settings. In this mode
various system settings can be carried out. To do the same,
use the keys and select the type of parameters to be
edited. The types of parameters that can be edited are:
General & IO
System
Fault
Step
Utilization counter: Bank operations utilization counters.
After selecting the type, press ENTER to enter the sub-menu of
that specific type.
The details of these sub-menus for every type is given further.
You can edit all these sub-menu settings by using the ENTER,
, , , and keys
To come out of the sub-menu press PROGRAM key once.
To store the edited parameters permanently, press SAVE when
you are either in the Edit Parameters or any sub-menu area.
To come out of Edit Parameters without saving the changes
press PROGRAM key again.
Note: In the Edit Parameters area, if no keys are pressed for
more than a minute, the default display screen comes on and
the changes done till that time are discarded.
TAS POWERTEK PVT.LTD.
: For general settings.
: For mains/generator system settings.
: Fault settings.
: Capacitor bank step settings.
VERSION 1.0