General & Io; System - TAS POWERTEK APFC-05 User Manual

Automatic power factor controller
Table of Contents

Advertisement

General & IO
PASSWORD
Enable
: 1
CHANGE PASSWORD
: 0001
LOAD DEFAULT
No
: 0
THD TO DISPLAY R/F
F-THD
: 1
UNIT ID
0000

System

Meas. Voltage
: 240
EXT-PT Ratio
0001.0:1
CUR CT Primary
Mains
: 1000
PF Up Lim :
Mains
[Ind :1]
0.980
PF Up Lim: Mains
Ind : 1
[0.980]
PF Low Lim: Mains
[Ind :1] 0.970
PF Low Lim: Mains
Ind :1 [0.970]
Auto kW Polr Chk
Disable: 0
TAS POWERTEK PVT.LTD.
Password: Enable or disable password.
Value: 0=Disable, 1=Enable.
Change Password: Set new value of password (4
digit). Factory default password is "0000"
Load Default: Loads factory set default parameters.
0=No, 1=Yes.
THD to Display: Type of THD to be displayed for V, I.
Unit ID: Allows Users to assign a Unique, 4-Digit
Identification Number to this APFC Unit.
Measured Voltage: Factory set parameter dependent
on hardware. For viewing only.
Ext-PT ratio: By default set to 0001.0:1, but in case
external PT is used, this ratio can be set. Limits:
Lower: 0000.1
Cur CT Primary: (Mains ): Feedback
source current for mains (if used with summation
CTs). Limits: Lower: 0001 Upper: 9999.
Power Factor Limits: APFC-05 has one set point for
Mains. upper & lower limits can be defined as Upper
PF and Lower PF. PF limits can be set as inductive or
capacitive.
Auto kW Polr Chk: Allows user to correct the kW
Reading to a Positive Value to indicate Energy
"Import" without reversing the CT Polarity in case
the kW reading is a –Ve value.
VERSION 1.0
Upper: 6000.0
- 22 -