Specifications

Regulatory Specifications

Certifications

The Radian GS3548E and GS7048E are certified to the following standards:
This product has been ETL certified to meet the following standards:
IEC 62109-1:2010 and IEC 62109-2:2011 — Safety of Power Converters for use in Photovoltaic Systems (2010)
o
IEC 62477-1:2012 — Safety Requirements for Power Electronic Converter Systems and Equipment
o
EN 61000-6-1 — EMC Standard: Immunity for Residential, Commercial, and Light-Industrial Environments
o
EN 61000-6-3 — EMC Standard: Emissions for Residential, Commercial, and Light-Industrial Environments
o
EN 61000-3-3 — EMC Standard: Limitation of Voltage Changes, Voltage Fluctuations, and Flicker in Public
o
Low-Voltage Supply Systems
AS/NZS 4777.2 — Grid Connection of Energy Systems via Inverters
o
AS/NZS 3100 — General Requirements for Electrical Equipment
o

Compliance

RoHS: per directive 2011/65/EU
o

Specification Conformity

This inverter/charger product conforms to AS/NZS 4777.2 for single inverter installations only.
o
A complete list of regulatory specifications is available on the Declaration of Conformity which
is included with the inverter.
NOTE :
The reconnection delay has a default setting of 5 minutes. The grid-interactive default
settings are shown in the Grid Interface Protection Menu portion of Table
The Grid Interface Protection settings are adjustable. However, this is only available to
operators with installer-level access. The reason for this limitation is that there are firm rules
concerning the acceptable voltage range, frequency range, clearance time during power loss,
and reconnect delay when exporting power back to the utility. The rules differ in different
locations around the world, although generally it is expected that the settings cannot be altered
by the end user. For this reason, the installer password must be changed from the default to
get access to these settings.
Once this password has been changed, the Grid Interface Protection settings can be
accessed by using the installer password.
See Grid Tied mode on page 14 for more information. Also see Default Settings and Ranges
on page 63.