3.10 CO2 REGULATION

During the complete calibration (Par. 3.9) it is possible to modify the CO
In order to have an exact value of
In case of calibration for propane air, select the analyser in LPG gas mode.
Check that theCO
value is the one indicated in the table (Par. 4.2), (considering a maximum tolerance of ± 0.2%), otherwise change the
2
value as described below:
During calibration, when the "
CO
value by pressing the buttons 5 or 6 (
2
In this phase, the previously activated icons together with the "external connected devices presence icon" (
and the operating temperature alternated with combustion setting is displayed.
Once the parameter has been altered wait for the value to be saved (displayed via the "
To confirm the value set, press "
2 in the flue gas, the technician must insert the sampling probe into the well to the bottom
CO
" symbol starts flashing (indicating the correct acquisition of the parameters) it is possible to alter the
).
To increase the combustion setting, press the button 5 ( ), to decrease it, press
the button 6 ( ). As the combustion setting increases, the CO
and vice-versa.
48
" followed by "
" again in order to go to the next calibration.
values.
2
" symbol flashing).
) will flash on the display
value decreases
2
71