Immergas VICTRIX OMNIA Manual page 70

Hide thumbs Also See for VICTRIX OMNIA:
Table of Contents

Advertisement

Ignition intermediate heat output
Once the nominal heat output calibration is confirmed, the appliance is calibrated with the intermediate heat output (or ignition heat
output).
At this stage the display features flashing icons: "
output (e.g.: 41%) is displayed; once the parameters are detected and stabilised, the "
nominal heat output settings have been set.
Minimum heat output
After having calibrated the boiler with the intermediate heat output, it is calibrated with the minimum heat output.
At this stage the display features flashing icons: "
output (0%) is displayed; once the parameters are detected and stabilised, the "
heat output settings have been set.
Calibration self-check
Once calibration operations are complete, the boiler runs a self-check for about one minute. During this check, the boiler can run at dif-
ferent powers and it is not possible to apply modifications to the operating parameters or to delete the operation in progress. Moreover, it
is important not to cut the boiler's power.
70
" and "
" and the operating temperature alternated with the current operating heat
Only after the "
(Par. 3.10) or switch to the next heat output parameter by pressing the "
button.
46
" and "
" and the operating temperature alternated with the current operating heat
Only after the "
(Par. 3.10) or switch to the calibration self-check phase by pressing the "
button.
47
" symbol will start flashing, meaning that the
" symbol flashes is it possible to change the CO
" symbol will start flashing, meaning that the minimal
" symbol flashes is it possible to change the CO
value
2
"
value
2
"