Prerequisites
Replace only one fan at a time. Fans are N+1 redundant.
Verify that all other fans are installed for proper redundancy and that their LEDs are green before replacing a fan.
Verify the status of the fan to be replaced by reviewing rear panel LEDs and buttons (see Front panel LEDs and
buttons).
Make sure that your configuration can support your actions. If the proper redundancy is not in place, power down the
D6020 before beginning this procedure.
For best cooling practices, do not operate the enclosure for more than 10 minutes when:
The system is powered on
More than one component or blank is removed
After removing an active component, promptly replace it with a blank or the appropriate component.
Procedure
1. Make sure that the disk drive drawer is closed.
2. Remove the fan.
3. To replace the fan:
a. Insert the fan in to the fan bay.
b. Push until the fan locks into place.

Removing and replacing the hot-pluggable I/O module

Prerequisites
Verify that the disk drive drawer is closed and the software solution indicates that the module is safe to remove.
Verify the status of the I/O module to be replaced by reviewing rear panel LEDs and buttons (see Rear panel
components).
For best cooling practices, do not operate the enclosure for more than 10 minutes when: