12.2 Indoor Unit

12.2.1
How to Fix Installation Plate
The mounting wall shall be strong and solid enough to prevent it from vibration.
Measuring Tape
MRZ16***,
MRZ20***,
RZ25***,
RZ35***,
RZ42***,
RZ50***
The center of installation plate should be at more than 1 at right and left of the wall.
The distance from installation plate edge to ceiling should more than 2.
From installation plate center to unit's left side is 3.
From installation plate center to unit's right side is 4.
B  For left side piping, piping connection for liquid should be about 5 from this line.
 For left side piping, piping connection for gas should be about 6 from this line.
1
Mount the installation plate on the wall with 5 screws or more (at least 5 screws).
(If mounting the unit on the concrete wall, consider using anchor bolts.)
Always mount the installation plate horizontally by aligning the marking-off line with the thread and using
o
a level gauge.
2
Drill the piping plate hole with ø70 mm hole-core drill.
Line according to the left and right side of the installation plate. The meeting point of the extended line is
o
the center of the hole. Another method is by putting measuring tape at position as shown in the diagram
above. The hole center is obtained by measuring the distance namely 115 mm for left and right hole
respectively.
Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor
o
side.
12.2.2
To Drill a Hole in the Wall and Install a Sleeve of Piping
1
Insert the piping sleeve to the hole.
2
Fix the bushing to the sleeve.
3
Cut the sleeve until it extrudes about 15 mm
from the wall.
When the wall is hollow, please be sure to use
the sleeve for tube assembly to prevent dangers
caused by mice biting the connection cable.
4
Finish by sealing the sleeve with putty or
caulking compound at the final stage.
Wall
More than
3
168 mm
PIPE
HOLE
CENTER
115mm TO
HOLE CENTER
115 mm
Model
1
465 mm
CAUTION
Ceiling
1
More
2
screw
than
2
6
Installation plate
5
For best strength of INDOOR
unit installation, it is highly
recommended to locate " "
at 5 position as shown.
Dimension
2
3
70 mm ( * )
365 mm
Sleeve for tube
assembly
ø70 mm through hole
55
More than
1
Indoor unit
4
216 mm
1
PIPE
HOLE
CENTER
115mm TO
HOLE CENTER
115 mm
4
5
415 mm
10 mm
70 mm
Dimension 2
(*) :-
If holder at the rear of chassis
(Refer column "12.2.3 Indoor
Unit Installation") need to be
used to prop up the unit, this
distance shall be 85 mm or
more.
Wall
Indoor
Outdoor
15 mm
Wall
6
Approx. 5 - 7 mm
Bushing for tube
assembly
Putty or caulking compound