2. SETUP (ADVANCED OPTIONS)
SETUP
OUTPUTS
FLOAT 1
Fig. 62. Setup - Outputs - Floating Relay - Menu.
SETUP
OUTPUTS
FLOAT 1
ACTUATOR
Fig. 63. Setup - Outputs - Floating Relay - Actuator.
SETUP
OUTPUTS
FLOAT 1
INTEGRAL
Fig. 64. Setup - Outputs - Floating Relay - Integral.
SETUP
OUTPUTS
FLOAT 1
TYPE
ACTUATOR
INTEGRAL
DERIVATIV
SCHEDULE
RESET
EXIT
M24528
SETUP
OUTPUTS
FLOAT 1
ACTUATOR
90
SEC
ENTER
ACTUATOR
TIMING FOR
FLOAT 1
M24529
SETUP
OUTPUTS
FLOAT 1
INTEGRAL
400
SEC
ENTER
INTEGRAL
TIME FOR
FLOAT 1
M24530
T775A/B/M SERIES 2000 CONTROLLER
2.3.4.1.1. Floating Relay Menu
The Floating option is only available on the T775B2016,
T775B2024, T775B2032, and T775B2040 models.
When Relay 1 or Relay 3 is setup as floating, relays are
paired and the Float 1 or Float 2 menu displays with the
selections shown in Fig. 62.
2.3.4.1.1.1. ACTUATOR
The Actuator option displays only on the T775B2016,
T775B2024, T775B2032, and T775B2040 models when
the Type option = Floating.
1. From the menu, use the
light ACTUATOR.
2. Press the
button to display the actuator value.
3. Use the
and
desired number of seconds.
Default: 90 seconds
Range: 0 to 3,600 seconds)
4. Press the
button to accept the value and display
the INTEGRAL option.
The actuator run time is defined as the time needed to
move the actuator from the fully closed to fully open
position and visa versa.
2.3.4.1.1.2. INTEGRAL (
The Actuator option displays only on the T775B2016,
T775B2024, T775B2032, and T775B2040 models when
the Type option = Floating.
1. From the menu, use the
light INTEGRAL.
2. Press the
button to display the actuator value.
3. Use the
and
desired number of seconds.
Default: 400 seconds
Range: 0 to 3,600 seconds)
4. Press the
button to accept the value and display
the DERIVATIV option.
See Integral NOTES on page 22 for additional information
about setting the Integral time.
27
(floating relay only)
and
buttons to high-
buttons to increase/decrease the
modulating/floating relay only)
and
buttons to high-
buttons to increase/decrease the
62-0254–03

Advertisement

loading